V5 series inverter
47
9. Simple PLC operation parameters (Group P8)
Group P8: Simple PLC operation parameters
Parameters Name Range
Minmum
unit
Default
setting
Change
P8.00 Simple PLC operation
mode selection
0000~1113
Lowest bit: mode selection
0: Disabled
1: Stop after single cycle
2: keep the final value after single cycle
3: continuous cycle
Ten bit: PLC pause and restartup mode selection
0: Run again from stage 1
1: Continue running from the pause frequency
Hundred bit: save PLC parameter when power off
0: Not saving
1: Save the frequency when power off
Thousand bit: time unit of stage running
0: second
1: minute
1 0000 ×
P8.01 Stage 1 setup 000~621
Lowest bit: frequency setup
0: Multi I (i1~7)
1: Frequency P0.01
Ten bit: Operating direction selection
0: Run forward
1: Run reverse
2: Decided by operating instructions
Hundred bit: Acc/Dec time selection
0: Acc/Dec time 1
1: Acc/Dec time 2
2: Acc/Dec time 3
3: Acc/Dec time 4
4: Acc/Dec time 5
5: Acc/Dec time 6
6: Acc/Dec time 7
1 000
P8.02 Operating time of stage 1 0.1~6000.0 0.1 10.0
P8.03 Stage 2 setup 000~621 1 000
P8.04 Operating time of stage 2 0.1~6000.0 0.1 10.0
P8.05 Stage 3 setup 000~621 1 000
P8.06 Operating time of stage 3 0.1~6000.0 0.1 10.0
P8.07 Stage 4 setup 000~621 1 000
P8.08 Operating time of stage 4 0.1~6000.0 0.1 10.0
P8.09 Stage 5 setup 000~621 1 000
P8.10 Operating time of stage 5 0.1~6000.0 0.1 10.0
P8.11 Stage 6 setup 000~621 1 000
P8.12 Operating time of stage 6 0.1~6000.0 0.1 10.0
P8.13 Stage 7 setup 000~621 1 000
P8.14 Operating time of stage 7 0.1~6000.0 0.1 10.0