VESDA by Xtralis VESDA VLI Product Guide
www.xtralis.com 63
7. Insert the long tube near the Secondary Foam Filter Carstick connector and lower the chamber whilst
inserting (Figure 7-17).
Figure 7-17: Insert Long Tube
8. Insert the long tube until the white tape touches the Carstick connector.
Figure 7-18: Complete Long Tube Insertion
9. Insert the two chamber screws (Figure 7-8).
10. Reinstall the Intelligent Filter. Refer to Section 7.3 on page 55 for further information.
11. Power up the detector by reconnecting the 24 Volt input.
12. Wait approximately 10 minutes to ensure that the detector does not report any fault conditions.
13. Perform a smoke test and ensure detector response is as per commissioning data.