Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 4
Uninterrupble Power Supply
1 Safety and EMC Instrucons
Safety Instrucons
Please read carefully the following user manual and the safety instrucons before installing the UPS or using the
UPS! Please comply with all warnings and operang instrucons in this manual. Save this manual and read care-
fully the following instrucons before installing the unit. Do not operate this unit before reading through all safety
informaon and operang instrucons carefully.
1.1 Transportaon and Storage
• Please transport the UPS system only in the original packaging to protect against shock and impact.
• The UPS must be stored in a room where it is venlated and dry.
1.2 Preparaon
• Condensaon may occur if the UPS system is moved directly from cold to warm environments. The UPS
system must be absolutely dry before being installed. Please allow at least two hours for the UPS system
to acclimate to the environment.
• Do not install the UPS system near water or in moist environments.
• Do not install the UPS system where it would be exposed
1.3 Installaon
Do not connect appliances or devices which would overload the UPS (e.g. motor-type equipment) to the
UPS output receptacles or terminal.
• Place cables in such a way that no one can step on or trip over them.
• Do not block air vents in the housing of the system components. The UPS system must be installed in a
locaon with good venlaon. Ensure enough space on each side for venlaon.
UPS has provided a ground terminal for equipotenal earth bonding to the external UPS baery cabinets
in the nal installed system conguraon.
• The UPS can be installed only by qualied maintenance personnel.
• An appropriate disconnect device for short-circuit backup protecon should be provided in the building
wiring installaon, upstream of the UPS.
An integral single emergency switching device which prevents further supply to the load by the UPS in
any mode of operaon should be provided in the building wiring installaon.
• Connect the ground before connecng to the building wiring terminal.
• Installaon and wiring must be performed in accordance with the local electrical laws and regulaons.
1.4 Connecon
• This UPS must be installed and grounded in accordance with local and naonal electrical code.
The power supply for this unit must be single-phase rated in accordance with the equipment nameplate.
It also must be suitably grounded.
There can be no derivaon in the line that goes from the Backfeed Protecon to the UPS, as the standard
safety would be infringed.
The power supply for this unit must be single-phase rated in accordance with the equipment nameplate.
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
• Use of this equipment in life support applicaons where failure of this equipment can reasonably be
expected to cause the failure of the life support equipment or to signicantly aect its safety or eecve-
ness is not recommended. Do not use this equipment in the presence of a ammable anesthec mixture
with air, oxygen or nitrous oxide.