TX91 3.8- 10kVA Users Manual
Page 29
Uninterrupble Power Supply
4 Troubleshooting
If the UPS system is not functioning correctly, please reference the tables below to isolate the issue.
4.1 Audible Alarm
Descripon Buzzer status Can be Muted?
UPS status
Bypass mode Beeping once every 2 minutes
YesBaery mode Beeping once every 4 seconds
Fault mode Beeping connuously
Warning
Overload Beeping twice every second
Yes
Others Beeping once every second
Fault
All Beeping connuously Yes
4.2 Warning Indicator
Warning Icon (ashing) Alarm
Baery low
Beeping every second
Overload
Beeping twice every second
Baery unconnected
Beeping every second
Over charge
Beeping every second
EPO enable
Beeping every second
Fan failure/Over temperature
Beeping every second
Charger failure
Beeping every second
I/P fuse broken
Beeping every second
Overload 3 mes in 30min Beeping every second