26 Genyo plus, Additional Installation, Operation and Maintenance Instructions
6.4 Parameters for lack of water
Description
Parameters
Unit of
measurement
Default
Additional notes
8
The ART function
Ar0, disabled
Ar1, enabled
-
Ar0
ART automatic restart function in case of
triggering of the A01 lack of water or
A11 minimum pressure alarm: see
The
ART function on page 26
9
A01 lack of water alarm
nf0, disabled
nf1, enabled and
pump unit STOP
-
nf1
If nf1 is set, activation of the ART
function: see The ART function on page
26
9.1
Delay time till triggering of
alarm A01
r01 = 1 s
..
r5.0 = 5 min
s / min
r05
Can be activated with parameter 9 set
to nf1
Example: r2.5 = 2 min and 50 s
10
A11 minimum pressure
threshold
P0.0 = disabled
..
P8.0 = 8 bar (psi)
bar / psi
0.0
Alarm A11 is triggered if the
pressure does not reach the set
value
If not set at 0.0, activation of the
ART function: see The ART function
on page 26
10.1
Delay time till triggering of
alarm A11
t01 = 1 s
..
t5.0 = 5 min
s / min
t05
Example: t1.5 = 1 min and 50 s
6.5 Other parameters
Description
Parameters
Unit of
measurement
Default
Notes
11
A02 overcurrent alarm
c10 = 10%
..
c30 = 30%
%
c20
Percentage of overload of the current
absorbed by the motor for triggering
the overcurrent alarm
12
Loading the default parameters
rS0 = NO
rS1 = OK
-
rS0
-
6.6 The ART function
If the alarms A01 and/or A11 are triggered, an attempt is automatically made to restart the
pump unit:
After 5 minutes
If the alarms persist, every 30 minutes over the next 24 hours.
If the alarms continue to persist, the pump unit remains off with the LED (11) on.
Note: the alarms can be reset at any time by pressing the MENU/ENTER button (6).