Parameter Tables
5-13
b5-04
Integral Limit
Setting
Sets the I-control limit as a percentage of
the maximum output frequency.
0.0 to
100.0
100.0
%
Yes A A A 1A8H 6-95
PID I Limit
b5-05
Derivative Time Sets D-control derivative time in 1-sec-
ond units.
D-control is not performed when the set-
ting is 0.00.
0.00 to
10.00
0.00 s Yes A A A 1A9H 6-95
PID D Time
b5-06
PID Output Limit Sets the upper limit after PID-control as a
percentage of the maximum output fre-
quency.
0.0 to
100.0
100.0
%
Yes A A A 1AAH 6-95
PID Limit
b5-07
PID Offset
Adjustment
Sets the offset after PID-control as a per-
centage of the maximum output fre-
quency.
-100.0
to
+100.0
0.0% Yes A A A 1ABH 6-95
PID Offset
b5-08
PID Primary
Delay Time
Constant
Sets the time constant for low pass filter
for PID-control outputs in 1-second units.
Not usually necessary to set.
0.00 to
10.00
0.00 s Yes A A A 1ACH 6-95
PID Delay Time
b5-09
PID Output Level
Selection
Select forward/reverse for PID output.
0: PID output is forward.
1: PID output is reverse (highlights the
output code)
0 or 1 0 No A A A 1ADH 6-95
Output Level Sel
b5-10
PID Output Gain
Setting
Sets output gain.
0.0 to
25.0
1.0 No A A A 1AEH 6-95
Output Gain
b5-11
PID Output
Reverse Selection
0: 0 limit when PID output is negative.
1: Reverses when PID output is nega-
tive.
0 limit when reverse prohibit is selected
using b1-04.
0 or 1 0 No A A A 1AFH 6-95
Output Rev Sel
b5-12
PID Feedback
Reference Miss-
ing Detection
Selection
0: No detection of loss of PID feedback.
1: Detection of loss of PID feedback.
Operation continues during detection,
with the malfunctioning contact not
operating.
2: Detection of loss of PID feedback.
Coasts to stop during detection, and
fault contact operates.
0 to 2 0 No A A A 1B0H 6-96
Fb los Det Sel
b5-13
PID Feedback
Loss Detection
Level
Sets the PID feedback loss detection level
as a percent units, with the maximum out-
put frequency at 100%.
0 to 100 0% No A A A 1B1H 6-96
Fb los Det Lvl
b5-14
PID Feedback
Loss Detection
Ti
me
Sets the PID feedback loss detection level
in s units.
0.0 to
25.5
1.0 s No A A A 1B2H 6-96
Fb los Det Time
b5-15
PID Sleep Func-
tion Start Level
Set the PID sleep function start level as a
frequency.
0.0 to
120.0
0.0 Hz No A A A 1B3H 6-96
PID Sleep Level
b5-16
PID Sleep Delay
Time
Set the delay time until the PID sleep
function starts in seconds.
0.0 to
25.5
0.0 s No A A A 1B4H 6-96
PID Sleep Time
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector