10-12
Wiring Examples
This section provides wiring examples to connect peripheral devices to the main circuits, examples of wir-
ing a transformer to MxC I/O, and other aspects of MxC wiring.
Using a VS Operator
This example shows wiring for using a VS Operator. The VS Operator model number is JVOP-95• or JVOP-
96 •.
CIMR-ACA25P5 (200 V class 5.5 kW)
Fig 10.4
3-phase power
MCCB
T
S
R
MxC
Motor
IM
Ground to 100Ω max
Forward Run Command
(forward run when closed)
Reverse Run Command
(reverse run when closed)
Multi-function contact inputs
Sequence common (0 V)
Shield wire connection
terminal
Master speed (0 to 10 V, 20 kΩ)
Speed setting power (15 V, 20 mA)
Master speed (4 to 20 mA, 250Ω)
Fault contact output
P1
P2
PC
Multi-function contact
output (Default: Running
signal)
Frequency meter
MTR CAL
Multi-function
analog output
Multi-function
analog output
(Default: Output
frequency)
Open collector 1
(Default:
Zero-speed signal)
Open collector 2
(Default:
Speed agreement
signal)
Multi-function
output
common
Multi-function
open-collector
output 48 V,
50 mA max
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
JVOP-95, C-96 VS Operator
FWD RUN
RESET
MASTER
AUX
REV RUN
STOP
1
S1
S2
S3
S4
S5
S6
S7
SC
0 V
E
+V
A1
A2
AC
M1
M2
MA
MB
MC
AM
FM
AC
2
4
5
11
15
13
17
9
10
18
F1
F3
E
FREQ SET
SOURCE
RUN
FAULT
FM