EasyManua.ls Logo

YASKAWA CIMR-ACA4011 - Verify Mode

YASKAWA CIMR-ACA4011
389 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Modes
3-13
Verify Mode
The Verify Mode displays any parameters that have been changed from their default settings. This includes all
parameters that were changed by the user in the Programming Mode, and all parameters that were changed
when Auto-Tuning was performed. If no parameter settings have been changed, then the Verify Mode display
window will read, “None”.
The Verify Mode will not show parameters belonging to the A1: Initialization Settings group (i.e., all parame-
ters that start with A1-
), even if those parameters have been changed. The exception is A1-02, which will
appear if it has been changed from its default value.
The user can also change parameter settings while in the Verify Mode. Just as in the Programming Mode, use
the up arrow, down arrow, and SHIFT/RESET keys to adjust any setting values. Save changes by pressing the
DATA/ENTER key.
Using the Verify Mode
The example below demonstrates how to use the Verify Mode to view parameters that have been set to values
different from their default settings. In the example, the following parameters have been changed: b1-01 (Ref-
erence Selection), C1-01 (Acceleration Time 1), E1-01 (Input Voltage Setting), and E2-01 (Motor Rated Cur-
rent).
Fig 3.8 Operations in Verify Mode
** Main Menu **
-DRIVE-
Operation
** Main Menu **
-QUICK-
Quick Setting
** Main Menu **
-ADV-
Programming
** Main Menu **
-VERIFY-
Modified Consts
** Main Menu **
-A.TUNE-
Auto-Tuning
MENU
MENU
MENU
MENU
MENU
Monitor display Setting displayMode selection display
DATA
ENTER
Reference Source
-VERIFY-
b1-01=0
*0*
Terminals
ESC
DATA
ENTER
Accel Time 1
-VERIFY-
(0.06000.0)
10.0Sec
C1-01=200.0Sec
A B
A B
Reference Source
-VERIFY-
b1-01= 0
*0*
Terminals
DATA
ENTER
ESC
DATA
ENTER
ESC
DATA
ENTER
ESC
Input Voltage
-VERIFY-
(155255)
200VAC
E1-01=200VAC
Motor Rated FLA
-VERIFY-
(0.326.40)
1.90A
E2-01=2.00A
Motor Rated FLA
-VERIFY-
(0.326.40)
1.90A
E2-01= 2.00A
Input Voltage
-VERIFY-
(155255)
200V
E1-01= 200VAC
Accel Time 1
-VERIFY-
(0.06000.0)
10.0Sec
C1-01=0200.0Sec
DATA
ENTER
ESC
"1"
"1"

Table of Contents