3-12
External Fault Setting Procedure
The following diagram shows how to set one of the multi-function contact inputs to be triggered when an
external fault is detected. To make the setting changes, the MxC must be in the Advanced Programming
Mode.
Fig 3.7 External Fault Function Setting Example
** Main Menu **
-DRIVE-
Operation
** Main Menu **
-QUICK-
Quick Setting
** Main Menu **
-ADV-
Programming
** Main Menu **
-VERIFY-
Modified Consts
** Main Menu **
-A.TUNE-
Auto-Tuning
MENU
Digital Inputs
-ADV-
H1-01=24
Terminal S3 Sel
MENU
MENU
MENU
MENU
ESC
DATA
ENTER
Terminal S3 Sel
-ADV-
H1- 01 =24
External Fault
ESC
ESC
DATA
ENTER
RESET
Monitor display Setting displayMode selection display
*24*
1 2
A B
A B
Digital Inputs
-ADV-
H2-01= 0
Term M1-M2 Sel
Terminal S4 Sel
-ADV-
H1- 02 =14
*14*
Terminal S8 Sel
-ADV-
H1- 08 =08
Ext BaseBlk N.O.
*08*
Terminal S3 Sel
-ADV-
H1- 01= 24
NO/Always Det
*24*
Coast to Stop
Terminal S3 Sel
-ADV-
H1- 01= 25
NC/Always Det
*24*
Coast to Stop
Terminal S3 Sel
-ADV-
H1- 01= 26
NO/During RUN
*24*
Coast to Stop
Terminal S3 Sel
-ADV-
H1- 01= 27
NC/During RUN
*24*
Coast to Stop
Terminal S3 Sel
-ADV-
H1- 01= 2F
NC/During RUN
*24*
Alarm Only
3 4
3 4
1 2
DATA
ENTER
Fault Reset
Terminal S4 Sel
-ADV-
H1-02 =14
Digital Inputs
ESC
RESET
"24"
"14"
"08"
Terminal S8 Sel
-ADV-
H1-08 =08
Digital Inputs
ESC
RESET