Parameter Tables
5-25
E: Motor Parameter
The following settings are made with the motor parameter parameters (E parameters): V/f characteristics and
motor parameters.
E1: V/f Pattern
* 1. These are values for a 200 V class MxC. Double the value for a 400 V class MxC.
* 2. The default will change when the control method is changed. The Open Loop Vector defaults are given.
* 3. E1-11 and E1-12 are disregarded when set to 0.0.
* 4. E1-13 is set to the same value as E1-05 by Auto-Tuning.
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector
E1-01
Input Voltage
Setting
Set the MxC input voltage in 1 volt.
This setting is used as a reference value in
protection functions.
155 to
255
*1
200
VA C
*1
No Q Q Q 300H 6-104
Input Voltage
E1-03
V/F Pattern
Selection
0 to D: Select from the 14 preset pat-
terns.
F: Custom user-set patterns
(Applicable for settings E1-04 to
E1-10).
0 to D,
and F
FNoQQNo302H6-104
V/F Selection
E1-04
Maximum Out-
put Frequency
To set V/f characteristics in a straight
line, set the same values for E1-07 and
E1-09. In this case, the setting for E1-08
will be disregarded.
Always ensure that the four frequencies
are set in the following manner:
E1-04 (FMAX) E1-06 (FA) > E1-07
(FB) E1-09 (FMIN)
40.0 to
120.0
60.0
Hz
*2
No Q Q Q 303H 6-104
Max Frequency
E1-05
Maximum Out-
put Voltage
0.0 to
255.0
*1
200.0
VA C
*1 *2
No Q Q Q 304H 6-104
Max Voltage
E1-06
Base Frequency
0.0 to
120.0
60.0
Hz
*2
No Q Q Q 305H 6-104
Base Frequency
E1-07
Mid Output
Frequency A
0.0 to
120.0
3.0 Hz
*2
No A A No 306H 6-104
Mid Frequency A
E1-08
Mid Output
Voltage A
0.0 to
255.0
*1
13.0
VA C
*1 *2
No A A No 307H
4-14
6-104
Mid Voltage A
E1-09
Minimum Output
Frequency
0.0 to
120.0
0.5 Hz
*2
No Q Q A 308H 6-104
Min Frequency
E1-10
Minimum Output
Voltage
0.0 to
255.0
*1
2.5
VA C
*1 *2
No A A No 309H
4-14
6-104
Min Voltage
E1-11
Mid Output
Frequency B
Set only to fine-adjust V/f for the output
range. Normally, this setting is not
required.
0.0 to
120.0
0.0 Hz
*3
No A A A 30AH 6-104
Mid Frequency B
E1-12
Mid Output
Voltage B
0.0 to
255.0
*1
0.0
VA C
*3
No A A A 30BH 6-104
Mid Voltage B
E1-13
Base Voltage 0.0 to
255.0
*1
0.0
VA C
*4
No A Q Q 30CH 6-104
Base Voltage
Output voltage (V)
Frequency (Hz)
FMIN
(E1-09)
FB
(E1-07)
FA
(E1-08)
FA
(E1-04)
VC
(E1-08)
VMIN
(E1-10)
(E1-05)
(V BASE)
(E1-13)
VMAX

Table of Contents