EasyManua.ls Logo

YASKAWA CIMR-ACA4011 - Using Contact and Open Collector Outputs

YASKAWA CIMR-ACA4011
389 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10-16
Using Contact and Open Collector Outputs
This example shows wiring for digital outputs and open collector outputs.
The following example is for the CIMR-ACA25P5 (200 V class MxC for 5.5 kW).
Fig 10.8
MxC
U/T1
V/T2
W/T3
IM
Ground
MA
MB
MC
P2
PC
Multi-function
open collector output
48 Vdc 50 mA max
P1
(Default: zero speed)
M1
M2
Multi-function contact output
(Default: RUN)
T/L3
S/L2
R/L1
3-phase power
MCCB
T
S
R
FM
Multi-function analog output 1
AC
E(G)
-10 to +10 V 2 mA
AM
FM
Default: Output frequency,
0 to +10 V
Default: Ouput current,
0 to +10 V
-10 to +10 V 2 mA
Multi-function analog output 2
Frequency meter scale adjustment resistor
20 kǡ
Ammeter scale adjustment resistor
20 kǡ
Motor
Sequence external power
supply
SA
250 Vac max
30 Vdc max
Flywheel
diode
48 Vdc max
48 Vdc max
Sequence
(Default: Freq agree)
250 Vac, 10 mA min. 1 A max
30 Vdc, 10 mA min. 1 A max
250 Vac, 1 A max
30 Vdc, 1 A max
E(G)
Flywheel
diode
Flywheel
diode
Open collector 2
AM
P4
C4
P3
C3
48 Vdc max
48 Vdc max
Flywheel
diode
Flywheel
diode
Error contact output
Open collector 1