Parameter Tables
5-21
* The upper limit of the setting range depends on the upper limit set at E1-04. The maximum allowable setting is 120.00.
d2: Reference Limits
d1-13
Frequency
Reference 13
The frequency reference when multi-step
speed references 3 and 4 are on for multi-
function inputs (unit: Set in o1-03).
0.00 to
120.00
*
0.00
Hz
Yes A A A 28EH -
Reference 13
d1-14
Frequency
Reference 14
The frequency reference when multi-step
speed references 1, 3, and 4 are on for
multi-function inputs (unit: Set in o1-03).
0.00
Hz
Yes A A A 2 8FH -
Reference 14
d1-15
Frequency
Reference 15
The frequency reference when multi-step
speed references 2, 3, and 4 are on for
multi-function inputs (unit: Set in o1-03).
0.00
Hz
Yes A A A 290H -
Reference 15
d1-16
Frequency
Reference 16
The frequency reference when multi-step
speed references 1, 2, 3, and 4 are on for
multi-function inputs (unit: Set in o1-03).
0.00
Hz
Yes A A A 291H -
Reference 16
d1-17
Jog Frequency
Reference
The frequency reference when the jog
frequency reference selection, FJOG
command, or RJOG command is on (unit:
Set in o1-03).
6.00
Hz
Yes Q Q Q 292H
4-4
6-5
6-75
Jog Reference
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector
d2-01
Frequency Refer-
ence Upper Limit
Set the output frequency upper limit as a
percent, taking the max. output frequency
to be 100%.
0.0 to
110.0
100.0
%
No A A A 289H
6-30
6-70
Ref Upper Limit
d2-02
Frequency Refer-
ence Lower Limit
Sets the output frequency lower limit as a
percentage of the maximum output fre-
quency.
0.0 to
110.0
0.0% No A A A 28AH
6-30
6-70
Ref Lower Limit
d2-03
Master Speed
Reference Lower
Limit
Set the master speed reference lower limit
as a percent, taking the max. output fre-
quency to be 100%.
0.0 to
110.0
0.0% No A A A 293H
6-30
6-70
Ref1 Lower Limit
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector