Speed Limit (Frequency Reference Limit Function)
6-31
Adjusting Frequency Lower Limit Using an Analog Input
If H3-09 (Terminal A2 Function Selection) or H3-05 (Terminal A3 Function Selection) is set to 9 (output fre-
quency lower level), the frequency lower level can be adjusted using the terminal A2 input level.
Fig 6.33 Output Frequency Lower Level for Multi-function Analog Input
INFO
If parameter d2-02 and the terminal A2 output frequency lower level have been set at the same time, the
larger value will become the frequency lower limit.
Output frequency lower level
0 V
(4 mA)
Multi-function analog input
terminal A2 or A3 input level
10 V
(20 mA)
Max output frequency
E1-04