Test Run Procedures
4-5
* 1. 0 or 1 for Flux Vector Control.
* 2. The setting range for accel/decel times depends on the setting of C1-10 (Accel/Decel Time Setting Unit). If C1-10 is set to 0, the setting range is 0.00 to
600.00 (s).
* 3. Fixed to 2:4 kHz for V/f.
For Open Loop Vector Control, can select from 2:4 kHz or 4:8 kHz (Fixed to 2: 4 kHz for 200 V class MxC for 45 kW and 400 V class MxCs for 22 kW
and 45 kW).
* 4. Displayed only while using Flux Vector Control.
E2-01
Motor Rated Cur-
rent
Sets the motor nameplate full load current in
amperes (A). This value is automatically set
during Auto-Tuning.
10% to 200%
of MxC's rated
current
Setting for
general-
purpose
motor of
same
capacity
as MxC
5-26
6-51
6-102
F1-01
*4
PG Parameter
Sets the number of pulses per revolution (PPM)
of the encoder (pulse generator).
0 to 60000 600 5-29
H4-02 and
H4-05
FM and AM
terminal output
Gain
Set the voltage level gain for the multi-function
analog output 1 (H4-02) and 2 (H4-05).
Set the number of multiples of 10 V to be output
as the 100% output for the monitor item.
0.00 to 2.50
H4-02:
1.00
H4-05:
0.50
5-41
L1-01
Motor Overload
Protection Selec-
tion
Sets the motor thermal overload protection
(OL1) based on the cooling capacity of the
motor.
0: Disabled
1: General-purpose motor protection
2: Inverter motor protection
3: Vector motor protection
0 to 3 1
5-43
6-51
Table 4.1 Parameters that Must Be Set (Continued)
Parameter
Number
Name Description
Setting
Range
Default Page