38
Drive Parameter Listing
(n018-n035) Section 8
PARA- SETTING RANGE SETTING FACTORY USER PARA.
METER NAME (AND UNITS) INCREMENT SETTING SETTING REF.
n018
Accel/Decel Time 0: 0.1
1 (sec) .2
Setting Unit 1: 0.01
n019 Acceleration Time 1 (Note 4) 0.00 to 600.0
0.01 sec
n020 Deceleration Time 1 (Note 4) or or
5.2
n021 Acceleration Time 2 (Note 4) 0.0 to 6000 0.1 (sec)
10.0
n022 Deceleration Time 2 (Note 4) (Dependent on n018 setting)
0: No S-curve
n023 S-curve Selection
1: 0.2 second
10
0
5.3
2: 0.5 second
3: 1.0 second
n024 Frequency Reference 1 (Note 4) 6.00
n025 Frequency Reference 2 (Note 4) 0.00
n026 Frequency Reference 3 (Note 4) 0.01 (Hz) 0.00
n027 Frequency Reference 4 (Note 4) 0.00 to 400.00 (< 100 Hz) 0.00
n028 Frequency Reference 5 (Note 4) or 0.00 5.11
n029 Frequency Reference 6 (Note 4) 0.1 (Hz) 0.00
n030 Frequency Reference 7 (Note 4) (>= 100 Hz) 0.00
n031 Frequency Reference 8 (Note 4) 0.00
n032 Jog Frequency Reference (Note 4) 6.00 5.12
n033
Frequency Reference Upper
0. to 110
1(%) 100
Limit
5.9
n034
Frequency Reference Lower
0. to 110
1(%) 0
Limit
0: 0.01 Hz (less than 100 Hz) / 0.1 Hz
n035
Digital Operator 1: 0.1%
10 5.30
Display Mode 2 - 39: rpm
40 - 3999: custom
Drive Parameters - Continued