10 Attachment
296 YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
Main Circuit Wire Gauges and Tightening Torques (for UL Standards)
Three-Phase 200 V Class
Model Terminal
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening
Torque
Nm (inlb)
Size Shape
2001
R/L1, S/L2, T/L3 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
14
*2
14
*2
- M3.5
0.8 - 1.0
(7.1 - 8.9)
2002
R/L1, S/L2, T/L3 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
14
*2
14
*2
- M3.5
0.8 - 1.0
(7.1 - 8.9)
2004
R/L1, S/L2, T/L3 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 14 14 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
14
*2
14
*2
- M3.5
0.8 - 1.0
(7.1 - 8.9)