Standards Compliance
5
5.2 European Standards
YASKAWA SIEPC71061753C GA500 Technical Manual 177
Model Terminal
Recomm. Gauge
mm
2
Applicable Gauge
mm
2
Wire Stripping
Length
*1
mm
Terminal Screw
Size and Shape
Tightening Torque
Nm (lbfin)
4031
R/L1, S/L2, T/L3 6 4 - 10 10
M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3 6 4 - 10 10
M4
1.5 - 1.7
(13.5 - 15)
-, +1, +2 10 2.5 - 16 18
M5
2.3 - 2.5
(19.8 - 22)
B1, B2 2.5 2.5 - 4 10
M4
1.5 - 1.7
(13.5 - 15)
6
*2
6 - 16
*2
-
M6
5.4 - 6.0
(47.8 - 53.1)
4038
R/L1, S/L2, T/L3 10 4 - 16 10
M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3 6 2.5 - 10 10
M4
1.5 - 1.7
(13.5 - 15)
-, +1, +2 16 4 - 25 18
M5
2.3 - 2.5
(19.8 - 22)
B1, B2 4 2.5 - 6 10
M4
1.5 - 1.7
(13.5 - 15)
10 6 - 16 -
M6
5.4 - 6.0
(47.8 - 53.1)
4044
R/L1, S/L2, T/L3 16 4 - 25 18
M5
2.3 - 2.5
(19.8 - 22)
U/T1, V/T2, W/T3 10 4 - 16 18
M5
2.3 - 2.5
(19.8 - 22)
-, +1, +2 16 6 - 25 18
M5
2.3 - 2.5
(19.8 - 22)
B1, B2 6 4 - 10 10
M4
1.5 - 1.7
(13.5 - 15)
10 6 - 16 -
M6
5.4 - 6.0
(47.8 - 53.1)
4060
R/L1, S/L2, T/L3 25 6 - 35 18
M5
25 mm
2
2.3 - 2.5
(19.8 - 22)
35 mm
2
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3 16 4 - 25 18
M5
2.3 - 2.5
(19.8 - 22)
-, +1, +2 25 6 - 35 18
M5
25 mm
2
2.3 - 2.5
(19.8 - 22)
35 mm
2
4.1 - 4.5
(36 - 40)
B1, B2 10 2.5 - 16 10
M4
1.5 - 1.7
(13.5 - 15)
10 6 - 16 -
M6
5.4 - 6.0
(47.8 - 53.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use the closed-loop crimp terminals
to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire).
Connect a Fuse to the Input Side (Primary Side)
The drive circuit protection must comply with EN 61800-5-1:2007 for protection against a short circuit in the
internal circuitry. Connect semiconductor fuses on the input side for branch circuit protection.
Refer to Single-Phase 200 V Class on page 178, Three-Phase 200 V Class on page 178, and Three-Phase 400 V
Class on page 178 for more information about recommended fuses.