EasyManua.ls Logo

YASKAWA GA50U Series - Page 46

YASKAWA GA50U Series
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Electrical Installation
46 YASKAWA TOEPC71061752B GA500 Drive Installation & Primary Operation
Model Terminal
Recomm.
Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening
Torque
Nm (inlb)
Size Shape
2056
R/L1, S/L2, T/L3 4 10 - 2 18 M5
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3 4 10 - 2 18 M5
AWG 10
2.3 - 2.5
(19.8 - 22)
AWG 8
4.1 - 4.5
(36 - 40)
-, +1, +2 2 8 - 2 18 M5
4.1 - 4.5
(36 - 40)
B1, B2 8 12 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
6 8 - 4 - M6
5.4 - 6.0
(47.8 - 53.1)
2070
R/L1, S/L2, T/L3 2 6 - 1 20 M6
5 - 5.5
(45 - 49)
U/T1, V/T2, W/T3 2 8 - 1 20 M6
5 - 5.5
(45 - 49)
-, +1, +2 1 6 - 1/0 20 M6
5 - 5.5
(45 - 49)
B1, B2 8 12 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
4 6 - 4 - M6
5.4 - 6.0
(47.8 - 53.1)
2082
R/L1, S/L2, T/L3 1 6 - 1/0 20 M6
5 - 5.5
(45 - 49)
U/T1, V/T2, W/T3 2 6 - 1 20 M6
5 - 5.5
(45 - 49)
-, +1, +2 2/0 2 - 2/0 20 M6
5 - 5.5
(45 - 49)
B1, B2 6 10 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
4 6 - 4 - M6
5.4 - 6.0
(47.8 - 53.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-
loop crimp terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
8-4NS from JST Mfg. Co., Ltd.
R8-4S from NICHIFU Co.,Ltd.
P10-8R from PANDUIT Corp.

Table of Contents

Related product manuals