Setting Function Page
13 Reverse Jog
14 Fault reset
15 Fast Stop (N.O.)
17 Fast Stop (N.C.)
18 Timer function input
19 PID disable
1A Accel/decel time selection 2
1B Program lockout
1E Reference sample hold
20 to 2F Ext. pump fault
30 PID integral reset
31 PID integral hold
32
Multi-Step Speed
Reference 4
34 PID soft starter cancel
35 PID input level selection
40
Forward run command
(2-Wire sequence)
41
Reverse run command
(2-Wire sequence)
42
Run command
(2-Wire sequence 2)
43
FWD/REV command
(2-Wire sequence 2)
47 Node setup
51 Sequence Timer Disable
52 Sequence Timer Cancel
60 DC Injection Braking command
61
External Speed Search
command 1
62
External Speed Search
command 2
63 Field weakening
65 KEB Ride-Thru 1 (N.C.)
66 KEB Ride-Thru 1 (N.O.)
Setting Function Page
67 Communications test mode
68 High Slip Braking (HSB)
6A Drive enable
73 Low City Press
75 Up 2 command
76 Down 2 command
7A KEB Ride-Thru 2 (N.C.)
7B KEB Ride-Thru 2 (N.O.)
80 HAND Mode
81 HAND Mode 2
82
<1>
PI Switch to Aux
83 Alternate Multi-Setpoint (Q1-02)
84 Alternate Multi-Setpoint (Q1-03)
85 Alternate Multi-Setpoint (Q1-04)
88 Volute-Thermostat Normally Open
89 Volute-Thermostat Normally Closed
8C Disable Pre-Charge
8D Multi Setpoint 1
8E Multi Setpoint 2
8F Low Water Level
90 High Water Level
92 Reset Accum
95 Remove Drive Disable
A8 Secondary PI Disable (N.O.)
A9 Secondary PI Disable (N.C.)
AA Secondary PI Inverse Operation
AB Secondary PI Integral Reset
AC Secondary PI Integral Hold
AD Select Secondary PI Parameters
AF Emergency Override Forward Run
B0 Emergency Override Reverse Run
<1> Available in drive software versions PRG: 8552 and later.
Not available in drive models 4A0930 and 4A1200.
n
H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection
The drive has three multi-function output terminals. Table i.23 lists the functions available for these terminals using H2-01,
H2-02, and H2-03.
No. Parameter Name Setting Range Default
H2-01 Terminal M1-M2 Function Selection (relay) 0 to 192 37: During Frequency Output
H2-02 Terminal M3-M4 Function Selection (relay) 0 to 192
42: Pressure Reached
<1>
H2-03 Terminal MD-ME-MF Function Selection (relay) 0 to 192 E: Fault
<1> Default is F: Through Mode in drive software versions PRG: 8551 and earlier.
Table i.23 Multi-Function Digital Output Terminal Settings
Setting Function Page
0 During run
1 Zero speed
2 Speed agree 1
3 User-set speed agree 1
Setting Function Page
4 Frequency detection 1
5 Frequency detection 2
6 Drive ready
7 DC bus undervoltage
i.5 Start-Up Programming and Operation
60