Technical Tip: iQPump1000 Setup Procedure for Use with Seametrics AG2000 Flow Meter
Product(s): iQpump1000
Doc. No. TN.iQp.04
TN.iQp.04 ©2016 - Yaskawa America, Inc.
Revision 1 - 2016-04 Page 10 of 10
Reading Accumulation: Monitors U1-84 to U1-87
3.4 Refer to Table 3. Observe Monitors U1-84 to U1-87 to build digits for total accumulation.
Table 3. Example Accumulation Readings - iQpump1000 Display
Monitor No.
U1-84
U1-85
U1-86
U1-87
Total
Display Example
28
413
546
.245
Display Value
Meaning
28,000,000
413,000
546
.245
28, 413, 546.245 Gallons
TROUBLESHOOTING
Table 4 provides troubleshooting tips from the Seametrics Flow Meter instructions.
Table 4. Troubleshooting - AG2000 Flow Meter (from Seametrics LT-65200290-042115)
Problem
Probable Cause
Corrective action
Blank display
Dead battery
Replace battery pack.
Flow rate steadily
reads
zero when there is
flow
Flow is below cutoff
(very low)
Reading will resume when flow increases.
There is air in the meter
Reposition meter for full pipe.
Display reads [ - ]
Meter is installed
backward
Note flow direction arrow, reverse meter.
Flow rate
intermittently
drops when there is
flow
There is air in the meter
Reposition meter for full pipe or rotate to avoid
bubbles.
Erratic reading
Improperly equalized
Check for proper equalization.
Pulsing flow
Use external power source (allows more flow
averaging).
Rapidly changing
conductivity
(chemigation
applications)
Install chemigation line downstream of meter (or
enough upstream for thorough mixing of fluids
before meter).