10 Troubleshooting
YASKAWA ELECTRIC SIEP C730600 89C YASKAWA AC Drive Option SI-EP3 Technical Manual 53
Option Fault Monitors U6-98 and U6-99
The option can declare error/warning conditions via drive monitor parameters on the drive keypad as shown in Table 31.
Table 31 Option Fault Monitor Descriptions
Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option SI-EP3 status. U6-99 is cleared upon a network-issued fault reset and upon
power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99
stores the new fault status value.
Option Compatibility
Users may connect up to 3 options simultaneously depending on the type of option.
Refer to Table 32 for details.
Table 32 Option Compatibility
Fault Condition Fault Declared
Status Value
(U6-98/U6-99)
Description
No Fault N/A 0 No faults.
Force Fault EF0 3 Network sent a message to force this node to the fault state.
Network Link Down bUS 1300 No network link to option board.
Network Failure bUS 1301 Connection with PLC Timeout.
Default MAC Address None 1303
Factory default MAC Address programmed into the option. Return for
reprogramming.
No IP Address None 1304 No IP Address has been programmed into the option.
No Station Name None 1305 No Station Name has been programmed into the option.
Bad Station Name
Programmed
None 1306 Station Name Programmed is invalid and must be reprogrammed.
Init. Failure None 1307 Initialize error on power-up.
Permanent
Communication Loss
bUS 1308 Fatal error in MAC/PHY hardware, requires power cycle to recover.
Bad IP Configuration None 1309 Invalid IP/subnet/gateway address programmed into F7-01 to F7-12.
Option Card
<1> When connecting two PG option cards, use both CN5-B and CN5-C. When connecting only one PG option card, use the CN5-C connector.
<2> Not available for the application with Motor 2 Selection.
<3> Not available with 1000-Series drive models with a capacities between 450 and 630 kW.
<4> When you use the input status of AI-A3 and DI-A3 as a monitor, you can connect AI-A3 and DI-A3 to CN5-A, CN5-B, or CN5-C.
Connector Number of Cards Possible
PG-B3, PG-X3 CN5-B, C 2
<1>
PG-RT3
<2> <3>
, PG-F3
<2> <3>
CN5-C 1
DO-A3, AO-A3 CN5-A, B, C 1
SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3,
SI-ES3, SI-B3, SI-M3, SI-W3
<3>
, SI-EM3
<3>
,
SI-EN3
<3>
, SI-EP3, AI-A3
<4>
, DI-A3
<4>
,
SI-EN3D, SI-EM3D
CN5-A 1