EasyManua.ls Logo

YASKAWA U1000 - Page 108

YASKAWA U1000
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Drive Model
Wire Gauge
(AWG, kcmil)
Screw
Size
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
Code
<1>
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
Machine No. Die Jaw
4o0590
3/0
M12
80-12
YF-1
YET-300-1
TD-323
TD-312
TP-080 100-051-268
4/0 R100-12
TD-324
TD-312
TP-100 100-051-270
250
<2>
R150-12
TD-325
TD-313
TP-150 100-051-273
300 R150-12 TP-150 100-051-273
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
<2> Recommended wire gauges. Refer to local codes for proper selections.
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C (167 °F) 600 Vac UL-approved vinyl-sheathed insulation.
Drive Models 4o0720 to 4o0930
Table i.43 Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge
(AWG, kcmil)
Screw
Size
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
Code
<1>
X, Y, Z
U/T1, V/T2, W/T3
Machine No. Die Jaw
4o0720
1/0
M12
R60-12
YF-1
YET-300-1
TD-321
TD-311
TP-060 100-066-160
2/0 70-12
TD-322
TD-311
TP-080 100-054-036
4/0 R100-12
TD-324
TD-312
TP-100 100-051-270
250 R150-12
TD-325
TD-313
TP-150 100-051-273
300
<2>
R150-12 TP-150 100-051-273
4o0900
1/0
M12
R60-12
YF-1
YET-300-1
TD-321
TD-311
TP-060 100-066-160
2/0 70-12
TD-322
TD-311
TP-080 100-054-036
3/0 80-12
TD-323
TD-312
TP-080 100-051-268
4/0
<2>
R100-12
TD-324
TD-312
TP-100 100-051-270
250 R150-12
TD-325
TD-313
TP-150 100-051-273
300 R150-12 TP-150 100-051-273
4o0930
1/0
M12
R60-12
YF-1
YET-300-1
TD-321
TD-311
TP-060 100-066-160
2/0 70-12
TD-322
TD-311
TP-080 100-054-036
4/0
<2>
R100-12
TD-324
TD-312
TP-100 100-051-270
250 R150-12
TD-325
TD-313
TP-150 100-051-273
300 R150-12 TP-150 100-051-273
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
<2> Recommended wire gauges. Refer to local codes for proper selections.
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C (167 °F) 600 Vac UL-approved vinyl-sheathed insulation.
i.9 Standards Compliance