Harmonic Filter Modules
Table i.44 Harmonic Filter Module Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge
(AWG, kcmil)
Screw
Size
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
Code
<1>
R/L1, S/L2, T/L3
X, Y, Z
Machine No. Die Jaw
EUJ71180o.o
1/0
M12
R60-12
YF-1
YET-300-1
TD-321
TD-311
TP-060 100-066-160
2/0 70-12
TD-322
TD-311
TP-080 100-054-036
4/0 R100-12
TD-324
TD-312
TP-100 100-051-270
250 R150-12
TD-325
TD-313
TP-150 100-051-273
300
<2>
R150-12 TP-150 100-051-273
EUJ71181o.o
1/0
M12
R60-12
YF-1
YET-300-1
TD-321
TD-311
TP-060 100-066-160
2/0 70-12
TD-322
TD-311
TP-080 100-054-036
3/0 80-12
TD-323
TD-312
TP-080 100-051-268
4/0
<2>
R100-12
TD-324
TD-312
TP-100 100-051-270
250 R150-12
TD-325
TD-313
TP-150 100-051-273
300 R150-12 TP-150 100-051-273
EUJ71182o.o
1/0
M12
R60-12
YF-1
YET-300-1
TD-321
TD-311
TP-060 100-066-160
2/0 70-12
TD-322
TD-311
TP-080 100-054-036
4/0
<2>
R100-12
TD-324
TD-312
TP-100 100-051-270
250 R150-12 TD-325
TD-313
TP-150 100-051-273
30 R150-12 TP-150 100-051-273
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
<2> Recommended wire gauges. Refer to local codes for proper selections.
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C (167 °F) 600 Vac UL-approved vinyl-sheathed insulation.
n
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external
power supply shall be a UL Listed Class 2 power supply source or equivalent only.
Table i.45 Control Circuit Terminal Power Supply
Input / Output Terminal Signal Power Supply Specifications
Open Collector Outputs DM+, DM- Requires class 2 power supply
Digital Inputs S1 to S8, SN, SC, SP, HC, H1, H2
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
Analog Inputs / Outputs +V, -V, A1, A2, A3, AC, AM, FM
Pulse Train Input RP, AC
Pulse Train Output MP, AC
n
Drive Short Circuit Rating
The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac
maximum (200
V Class) and 480 Vac maximum (400 V class: 4Eoooo and 4Woooo), and 500 Vac maximum (400 V
class: 4Aoooo and 4Poooo) with built-in fuses manufactured by Hinode Electric Co., Ltd. and Mersen (or equivalent).
n
Branch Circuit Protection
For installation in the United States, provide branch circuit protection in accordance with the National Electrical Code (NEC)
and any appilcable local codes. Use UL classified fuses to fulfill this requirement.
For installation in Canada, provide branch circuit protection in accordance with the Canadian Electrical Code and any
applicable provincial codes. Use UL classified fuses to fulfill this requirement.
i.9 Standards Compliance