Drive Models 2o0028 to 2o0248 and 4o0011 to 4o0590
A
C
A
B
B
D
E
Side Clearance Top/Bottom Clearance
A – 50 mm (1.97 in) minimum
B –
30 mm (1.18 in) minimum
C – 200 mm (7.87 in) minimum
D – 120 mm (4.72 in) minimum
E – Airflow direction
Figure i.8 Correct Drive Installation Spacing
Note: IP20/NEMA 1, UL Type 1 enclosure and IP00/Open Type enclosure models require the same amount of space above and below the drive
for installation.
Drive Models 4o0720 to 4o0930 and Harmonic Filter Module
Side Clearance Top/Bottom Clearance
A
A
C
B
B
E
D
F
Drive Model
Harmonic
Filter Module
4o0720
A – 50 mm (1.97 in) minimum
B –
30 mm (1.18 in) minimum
C – 200 mm (7.87 in) minimum
D – 120 mm (4.72 in) minimum
E – 60 mm (2.36 in) minimum
F – Airflow direction
Figure i.9 Correct Drive Model 4o0720 and Harmonic Filter Module Installation Spacing
u
Instructions on Installation Using the Eye Bolts and Hanging Brackets
Eye bolts
and hanging brackets are used to install the drive or to temporarily lift the drive during drive replacement. Using the
eye bolts and hanging brackets, the drive can be installed in an enclosure panel or on a wall. Do not leave the drive suspended
by the wires in a horizontal or vertical position for long periods of time. Do not transport the drive over long distances. Read
the following precautions and instructions before installing the drive.
i.3 Mechanical Installation
20
YASKAWA ELECTRIC TOEP C710636 04D U1000 Industrial MATRIX Drive Quick Start Guide