<8.ParameterSummary>
42
IM01C25A01-01E
BRAINCommunicationParameterList
Instrumentstowhichapplicable:
F:Differentialpressuretransmitters
P:Absoluteandgaugepressuretransmitters
L:Flangemounteddifferentialpressuretransmitters
No. Parametername Item
R/W
*1
Content Defaultvalue
Applicablemodel
Upload
data
F P L
01 MODEL Model R EJX(forEJXseries)
EJA(forEJAseries)
—
02 TAGNo. Tagnumber R Asspecied
—
03 SELFCHECK Self-diagnostics R GOOD
—
A DISPLAY Measureddatadisplay
A10 OUTPUT Output(in%) R -2.5to110%
—
A11 PRES Measuredpressure
afterzeroadjustment
R UnitspeciedinC20
—
A15 OUTPUTmA Outputcurrent R 3.6000to21.600mA
—
A16 ENGR.OUTPUT Userscaledvalue R UnitspeciedinI30
—
A17 ENGR.EXP Exponents R UnitspeciedinI32
—
A20 SP% Staticpressure(in%) R -10to110%
—
—
A21 SP Staticpressureafter
zeroadjustment
R UnitspeciedinD30
—
—
A30 CAPSULETEMP Capsuletemperature R UnitspeciedinD40
—
A60 SELFCHECK Self-diagnostics R RefertoTable4.1Alarm
MessageSummary
—
B SENSORTYPE Sensortype
B10 MODEL Modelandcapsuletype R Modelandcapsuletype
—
B11 STYLENO. Stylenumber R Stylenumberofproduct
—
B20 PRESLRL Lowerrangelimit R UnitspeciedinC20
—
B21 PRESURL Upperrangelimit R UnitspeciedinC20
—
B22 PMINSPAN Minimumspan R UnitspeciedinC20
—
B30 SPLRL Lowerrangelimitfor
staticpressure
R UnitspeciedinD30
—
—
B31 SPURL Upperrangelimitfor
staticpressure
R UnitspeciedinD30
—
—
B32 SPMINSPAN Minimumspanforstatic
pressure
R UnitspeciedinD30
—
—
B60 SELFCHECK Self-diagnostics R SeeA60
—
C BASICSETUP Settingdata
C10 TAGNO. Tagnumber W 16alphanumericcharacters Asspecied
C20 PRESUNIT Measurementrange
unit
W mmH2O,mmAq,mmWG,
mmHg,Torr,kPa,MPa,
mbar,bar,gf/cm
2
,kgf/cm
2
,
inH2O,inHg,ftH2O,psi,
atm,Pa,hPa
kPa
C21 PRESLRV Lowerrangevalue W -32000to32000within
measurementrange
Asspecied
C22 PRESURV Upperrangevalue W -32000to32000within
measurementrange
Asspecied
C23 PRESPOINT Decimalplace W 0to4 2
C30 AMPDAMPING Dampingtimeconstant
atamplier
W 0.50(0.00)to100.00sec,
seeD50
2.00secoras
specied
C40 OUTPUTMODE Outputmode W LINEARorSUQAREROOT LINEARoras
specied
C60 SELFCHECK Self-diagnostics R SeeA60
—
*1: R/W:R=Readonly,W=Read&Write
*2: ThedefaultvalueshowsMWP(Maximumworkingpressure)ofthecapsule.
SincetheworkingpressurelimitvariesaccordingtotheModel,refertotheGeneralSpecicationssectionineachuser’smanual.