<8.ParameterSummary>
43
IM01C25A01-01E
No. Parametername Item
R/W
*1
Content Defaultvalue
Applicablemodel
Upload
data
F P L
D AUXSET1 Auxiliarysettingdata1
D10 LOWCUT Lowcut W 0.00to20.00% 10.00%
D11 LOWCUTMODE Lowcutmode W LINEARorZERO LINEAR
D15 H/LSWAP Impulsepiping
accessingdirection
W NORMALorREVERSE NORMAL
D16 H2OUNITSEL H2Ounitselect W @4degCor@20degC
(68.0F)
@4degC
D20 OUTLIMIT(L) Lowsideoutputlimiter W -2.50to110.00% -2.50%
D21 OUTLIMIT(H) Highsideoutputlimiter W -2.50to110.00% 110%
D22 REVOUTPUT Outputreversal W NORMALorREVERSE NORMAL
D25 BURNOUT CPUerror R HIGHorLOW
D26 ERROROUT Hardwareerror W BURNOUTDIRorHOLD BURNOUTDIR
D30 SPUNIT Staticpressureunit W SeeC20 MPa
D31 SPA/GSLCT Gauge/Absselectfor
staticpressure
W GAUGEorABSOLUTE ABSOLUTE
D32 ATM.PRESS Coefcientforgiven
gaugepressure
W UnitspeciedinD30 0.10133MPa
D33 SPLRV Lowerlimitofstatic
pressure
W -32000to32000within
measurementrange
0.0MPa
D34 SPURV Upperlimitofstatic
pressure*
2
W -32000to32000within
measurementrange
D35 SPPOINT Decimalplaceofstatic
pressure
W 0to4 1
D36 SPDAMPING Dampingtimeconstant
ofSP
W 0.00to100.00sec 2.00sec
D37 SPSELECT H/Lselectforstatic
pressure
W HIGHorLOW HIGH
D40 TEMPUNIT Temperaturesetting
unit
W degC,degF,orK degC
D50 QUICKRESP Quickresponse W OFForON(enable0.00to
0.50secatC30)
OFF
D55 WRTPROTECT Writeprotectindicator R NOorYES NO
D56 WRTENABLE Writeprotectrelease W 8alphanumericcharacters None
D57 NEWPASSWORD Usersetpasswordfor
writeprotect
W 8alphanumericcharacters None
D58 SOFTWRSEAL Softwareseal R BREAKorKEEP KEEP
D60 SELFCHECK Self-diagnostics R SeeA60
E AUXSET2 Auxiliarysettingdata2
E10 T.ZEROCMP Temperature
compensationmode
W OFForON OFF
E11 TEMPZERO Zeroshiftcompensation W -99.999to99.999%/degC 0.000%/degC
E30 BIDIREMODE Bidirectionalmode W OFForON OFF
E50 DOSELECT Contactoutputselect W INHIBIT,PRES,SP,TEMP,
PRES/SP,PRES/TEMP,
SP/TEMP,orPRES/SP/
TEMP
INHIBIT
E51 DOSIG.TYPE Signaltypeselect W OFFWHENALARMorON
WHENALARM
ONWHENALARM
E52 DOUTPUT Contactoutput R OFForON OFF
E60 SELFCHECK Self-diagnostics R SeeA60
*1: R/W:R=Readonly,W=Read&Write
*2: ThedefaultvalueshowsMWP(Maximumworkingpressure)ofthecapsule.
SincetheworkingpressurelimitvariesaccordingtotheModel,refertotheGeneralSpecicationssectionineachuser’smanual.
ParameterSummary
8

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA EJX Series and is the answer not in the manual?

YOKOGAWA EJX Series Specifications

General IconGeneral
BrandYOKOGAWA
ModelEJX Series
CategoryTransmitter
LanguageEnglish

Related product manuals