<8.ParameterSummary>
44
IM01C25A01-01E
No. Parametername Item
R/W
*1
Content Defaultvalue
Applicablemodel
Upload
data
F P L
G ALARMSET Alarmsetting
G10 PALMODE Alertmode W INHIBIT,HI.ALDETECT,
LO.ALDETECT,orHI/LO.
ALDETECT
INHIBIT
—
G11 PHI.ALVAL Highsidealertvalue W -32000to32000,unit
speciedinC20
100.000kPa
—
G12 PLO.ALVAL Lowsidealertvalue W -32000to32000,unit
speciedinC20
-100.000kPa
—
G20 SPALMODE Staticpressurealert
mode
W INHIBIT,HI.ALDETECT,
LO.ALDETECT,orHI/LO.
ALDETECT
INHIBIT
—
—
G21 SPHI.ALVAL Highsidealertvalueof
SP*
2
W -32000to32000,unit
speciedinD30
—
—
G22 SPLO.ALVAL Lowsidealertvalue
ofSP
W -32000to32000,unit
speciedinD30
0.00000MPa
—
—
G30 TALMODE Temperaturealertmode W INHIBIT,HI.ALDETECT,
LO.ALDETECT,orHI/LO.
ALDETECT
INHIBIT
—
G31 THI.ALVAL Highsidealertvalueof
temperature
W -50to130 120degC
—
G32 TLO.ALVAL Lowsidealertvalueof
temperature
W -50to130 -40degC
—
G50 AUTORECOVER Auto-recoverfrom
sensorerror
W OFForON ON
—
G60 SELFCHECK Self-diagnostics R SeeA60
—
H AUTOSET Automaticsetup
H10 AUTOPLRV Lowerrangevalueauto
setup
W -32000to32000,unit
speciedinC20
Asspecied
—
H11 AUTOPURV Upperrangevalueauto
setup
W -32000to32000,unit
speciedinC20
Asspecied
—
H20 AUTOSPLRV SPlowerrangevalue
autosetup
W -32000to32000,unit
speciedinD30
0.00000MPa
—
—
H21 AUTOSPURV SPupperrangevalue
autosetup*
2
W -32000to32000,unit
speciedinD30
—
—
H60 SELFCHECK Self-diagnostics R SeeA60
—
I DISPSET Displaysetting
I10 DISPOUT1 LCDoutput1 W PRES,PRES%,ENGR.
PRES,SP,orSP%
PRES%
I11 DISPOUT2 LCDoutput2 W PRES,PRES%,ENGR.
PRES,SP,SP%,or---
---
I12 DISPOUT3 LCDoutput3 W SeeI11 ---
I13 DISPOUT4 LCDoutput4 W SeeI11 ---
I20 PDISPMODE %displaymode W LINEARorSQUAREROOT LINEAR
I21 PRES%RESO %displayresolution W NORMALorHIGH
RESOLUTION
NORMAL
I30 ENGR.UNIT Usersetengineering
unit
W 8alphanumericcharacters
I31 EASYEUSET Engineeringunitselect W
—
I32 ENGR.EXP Exponents W ---,×10,×100,×1000 ---
I33 ENGR.LRV Usersetlowerrange
limit
W -32000to32000,unit
speciedinI30
0.00
I34 ENGR.URV Usersetupperrange
limit
W -32000to32000,unit
speciedinI30
100.00
I35 ENGR.POINT Decimalplaceofuser
set
W 0to4 1
I40 BARINDICATR Barindicator W OFForON ON
I41 POWERONINF Displaywhenpowering
on
W OFForON ON
—
I60 SELFCHECK Self-diagnostics R SeeA60
—
*1: R/W:R=Readonly,W=Read&Write
*2: ThedefaultvalueshowsMWP(Maximumworkingpressure)ofthecapsule.
SincetheworkingpressurelimitvariesaccordingtotheModel,refertotheGeneralSpecicationssectionineachuser’smanual.