<9.GeneralSpecications>
9-9
IM 01C25F01-01E
Item Description Code
MarineCerticate American Bureau of Shipping Type Approval
*3*5
WCA
Bureau Veritas Type Approval
*3*5
WCB
Det Norske Veritas Type Approval
*3*5
WCD
Lloyd’s Register of Shipping Type Approval
*3*4*5
WCL
Nippon Kaiji Kyokai (NK) Type Approval
*3*5
WCN
High Accuracy type
*22
High accuracy HAC
Painting Color change Ampliercoveronly
P
Ampliercoverandterminalcover,Munsell7.5R4/14 PR
Coating change Anti-corrosion coating
*6
X2
316 SST exterior parts
*7
316 SST name plate, tag plate and zero adjustment screw HC
Fluoro-rubber O-ring AllO-ringsofamplierhousing.Lowerlimitofambienttemperature:15°C (5°F) HE
Lightning protector Transmitter power supply voltage:
10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe type, 9 to 32 V DC for
Fieldbus communication type.)
Allowablecurrent:Max.6000A(1×40μs),Repeating1000A(1×40μs) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
A
Status output
*8
Transistor output (sink type)
Contact rating: 10.5 to 30 VDC, 120 mA DC(max) Low level: 0 to 2 VDC
AL
Oil-prohibited use Degrease cleansing treatment. K1
Degreasecleansingtreatmentwithuorinatedoillledcapsule.
Operating temperature 20 to 80°C( –4 to 176°F)
K2
Oil-prohibited use with
dehydrating treatment
Degrease cleansing and dehydrating treatment K5
Degreasecleansinganddehydratingtreatmentwithuorinatedoilledcapsule.
Operating temperature. 20 to 80°C( –4 to 176°F)
K6
Capsulelluid Fluorinatedoillledincapsule
Operating temperature 20 to 80°C( –4 to 176°F)
K3
Calibration units
*9
P calibration (psi unit)
(See Table for Span and
Range Limits.)
D1
bar calibration (bar unit) D3
M calibration (kgf/cm
2
unit) D4
Output limits and failure
operation
*10
Failure alarm down-scale: Output status at CPU failure and hardware error is
–5%, 3.2 mA DC or less.
*24
C1
NAMUR NE43 Compliant
Output signal limits:
3.8 mA to 20.5 mA
*25
Failure alarm down-scale: Output status at CPU
failure and hardware error is –5%, 3.2 mA DC or less.
C2
Failure alarm up-scale: Output status at CPU
failure and hardware error is 110%, 21.6 mA or more.
C3
Gold-plated diaphragm
*18
Surface of isolating diaphragm is gold plated, effective for hydrogen permeation. A1
Wired tag plate 304 SST tag plate wired onto transmitter N4
Datacongurationat
factory
*11
DatacongurationforHART
communication type
Software damping, Descriptor, Message
CA
DatacongurationforBRAIN
communication type
Software damping
CB
Advanced diagnostics
*19
Multi-sensing process monitoring
• Impulse line blockage detection
*20
• Heat trace monitoring
DG6
European Pressure
Equipment Directive
*21
PED 97/23/EC
Category: III, Module: H, Type of Equipment; Pressure Accessory-Vessel,
Type of Fluid; Liquid and gas, Group of Fluid: 1 and 2
PE3
MaterialCerticate
*12
Process connector M15
Pressure test/
Leaktestcerticate
Test Pressure: 200 kPa (2 kgf/cm
2
)
*13
Nitrogen(N
2
) Gas or Water
*17
Retention time: one minute
T05
Test Pressure: 2 MPa (20 kgf/cm
2
)
*14
T06
Test Pressure: 10 MPa (100 kgf/cm
2
)
*15
T07
Test Pressure: 50 MPa (500 kgf/cm
2
)
*16
T08
Test Pressure: 70 MPa (10150 psi)
*23
T15
High pressure-proof
structure
*26
Maximum working pressure: 70MPa.
HG

Table of Contents