<APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF RAMC>
A-4
All Rights Reserved. Copyright © 2006, Rota Yokogawa
IM 01R01B02-01E-E 5th edition October 01, 2020-00
A1.2 Al Function Block
Block name Analog Input Function Block
Slot 1
Abs.
Index
Parameter Sub-
Parameter
Label Data Type/
Structure
Read/
Write
Initial value Functional Description
16 BLOCK_OBJECT - DS-32 R/- - Indicates the following block characteristics
Reserved - Unsigned8 R/- 250: Not used For future use (not available)
Block_Object Block Object Unsigned8 R/- 0x02: Function
Block
Kind of block
Parent_Class Parent Class Unsigned8 R/- 0x01: Input Superior device classication
Class Class Unsigned8 R/- 0x01: Analog Input Device classication
Dev_Rev - Unsigned16 R/- 1 Assigned device driver versions
(e.g. EDD)
Dev_Rev_Comp - Unsigned16 R/- 1 Lowest device revision supported by
the device
DD_Revision - Unsigned16 R/- 1 For future use (not available)
Prole - OctetString R/- 0x40: PROFIBUS
PA Prole for
Process Control
Devices,
0x02: Compact
Class B
Used Prole
Prole_Revision - Unsigned16 R/- 0x0302: Version
3.02
Used Prole version
Execution_Time - Unsigned8 R/- 0 For future use (not available)
Number_of_
Parameters
No. of Parameters Unsigned16 R/- 45 Number of used parameters
Address_of_
View_1
- Unsigned16 R/- 0x01E6: slot 1,
index 230
Reference to VIEW_1 parameter
Number_of_Views - Unsigned8 R/- 2 Number of Views available
17 ST_REV Static Revision No. Unsigned16 R/- 0 Indicates the revision level of the
described block. Increments each time a
static parameter (S) changes
18 TAG_DESC TAG OctetString R/W Block specic TAG for customer use
19 STRATEGY Strategy Unsigned16 R/W 0 User-specied value e.g. for conguration
or diagnostics as a sorting key
20 ALERT_KEY Alert Key Unsigned8 R/W 0 User-specied value for event allocation
e.g. identication of the plant unit
21 TARGET_MODE Target Mode Unsigned8 R/W 0x08: AUTO
(permitted bit only!)
Indicates and sets the target mode of
the block
22 MODE_BLK - DS-37 R/- - Indicates block mode overview by
sub-parameters
Actual Actual Mode Unsigned8 R/- 0x08: AUTO
(permitted bit only!)
Indicates the current mode
Permitted - Unsigned8 R/- 0x08: AUTO
(permitted bit only!)
Indicates possible modes
Normal - Unsigned8 R/- 0x08: AUTO
(permitted bit only!)
Indicates the usual mode during normal
operation
23 ALARM_SUM - DS-42 R/- - Maintain alert status by sub-parameters
Current Current State
Alarm Sum
OctetString R/- 0x0000: No Alarm
(no modication
indicated)
Indicates Update Events (static parameter
modication)
Unacknowledged - OctetString R/- 0 For future use (not available)
Unreported - OctetString R/- 0 For future use (not available)
Disabled - OctetString R/- 0 For future use (not available)
24 BATCH - DS-67 R/W - Identication of available channels and
current batch in case of alerts
Batch_ID Batch ID Unsigned32 R/W 0 Input and indication of batch ID for
identication
Rup Batch Unit Unsigned16 R/W 0 Input and indication of active Control
Recipe Unit Procedure/related Unit
Operation Batch Operation Unsigned16 R/W 0 Input and indication of active Control
Recipe Operation
Phase Batch Phase Unsigned16 R/W 0 Input and indication of active Control
Recipe Phase
26 OUT - 101 R/W* - Cyclic indication of process variable/
input in manual block mode