<APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF RAMC>
A-8
All Rights Reserved. Copyright © 2006, Rota Yokogawa
IM 01R01B02-01E-E 5th edition October 01, 2020-00
Abs.
Index
Parameter Sub-
Parameter
Label Data Type/
Structure
Read/
Write
Initial value Functional Description
33 VOLUME_FLOW - 101 R/- - Indicates the measured volume ow
Value Volume Flow Float R/- - Volume ow value
Status Volume Flow
Status
Unsigned8 R/- - Volume ow status
34 VOLUME_FLOW_
UNITS
Volume Flow Unit Unsigned16 R/W Det. by ordered
scale
Volume ow unit selection and enabling
of measured variable (disables mass
ow)
35 VOLUME_FLOW_
LO_LIMIT
Volume Flow Low
Limit
Float R/W 0 % of ow span Sensor's lower range value (volume ow)
36 VOLUME_FLOW_
HI_LIMIT
Volume Flow High
Limit
Float R/W 100 % of ow span Sensor's upper range value (volume ow)
37 MASS_FLOW - 101 R/- - Indicates the measured mass ow
Value Mass Flow Float R/- - Mass ow value
Status Mass Flow Status Unsigned8 R/- - Mass ow status
38 MASS_FLOW_
UNITS
Mass Flow Unit Unsigned16 R/W Det. by ordered
scale
Mass ow unit selection and enabling
of measured variable (disables volume
ow)
39 MASS_FLOW_
LO_LIMIT
Mass Flow Low
Limit
Float R/W 0 % of ow span Sensor's lower range value (mass ow)
40 MASS_FLOW_HI_
LIMIT
Mass Flow High
Limit
Float R/W 100 % of ow span Sensor's upper range value (mass ow)
45 TEMPERATURE - 101 R/- - Measured on board temperature
Value Temperature Float R/- According to
ambient
temperature
Indicates the on board temperature
value
Status - Unsigned8 R/- 0x80: Good Not supported
46 TEMPERATURE_
UNITS
Temperature Unit Unsigned16 R/W 1001: °C On board temperature unit selection
69 OPER_VISCOSITY Viscosity Float R/- Det. by ordered
scale
Indicates uid's viscosity conguration
value
70 OPER_VISCOSITY
_UNIT
- Unsigned16 R/- Det. by ordered
scale
Congurated unit of uid's viscosity
71 OPER_PRESSURE Pressure Float R/- Det. by ordered
scale
Indicates uid's pressure conguration
value
72 OPER_PRESSURE
_UNIT
- Unsigned16 R/- Det. by ordered
scale
Congurated unit of uid's pressure
73 OPER_PRESSURE
_REF
Ref. Pressure Float R/- Det. by ordered
scale
Indicates uid's pressure reference
conguration value
74 OPER_PRESSURE
_REF_UNIT
- Unsigned16 R/- Det. by ordered
scale
Congurated unit of uid's pressure
reference
75 OPER_
TEMPERATURE
Temperature Float R/- Det. by ordered
scale
Indicates uid's process temperature
conguration value
76 OPER_
TEMPERATURE_
UNIT
- Unsigned16 R/- Det. by ordered
scale
Congurated unit of uid's process
temperature conguration unit
77 OPER_
CONDITION
Oper. Condition Unsigned8 R/- Det. by ordered
scale
Indicates congured uid's pressure
operation condition
78 OPER_FLUID_
PHASE
Fluid Phase Unsigned8 R/- Det. by ordered
scale
Indicates uid's operation condition
79 OPER_FLOW_
REFERENCE
Flow Reference Unsigned8 R/- Det. by ordered
scale
Indicates uid's operation ow reference
80 DEVICE_SERIAL_
NO
Serial Number
(S/N)
OctetString R/- Det. by ordered
device
Indicates the serial number of the
device
81 DEVICE_MODEL_
CODE
Model Code OctetString R/- Det. by ordered
device
Indicates the model code of the device
82 OPER_FLUID_
NAME
Fluid Name OctetString R/- Det. by ordered
scale
Indicates uid's name
83 TOTALIZER Totalizer Float R/- 0 Indicates totalized value (volume or
mass) of the enabled process variable
84 TOTALIZER_UNIT Totalizer Unit Unsigned16 R/W Det. by ordered
scale
Indicates totalizer unit
85 TOTALIZER_
RESET
Totalizer Reset Unsigned8 R/W - Performs totalizer reset to zero
86 RESET_ERROR_
BIT
Reset Errors Unsigned8 R/W - Execution resets specic error bits
87 DIST_OPTION_
A16
Device Version Unsigned8 R/- Det. by ordered
device
Indicates the mechanical indicator
version (Distance: option /A16)
88 SCALE_SPAN_
VALUE
Scale 100% Value Float R/- Det. by ordered
scale
Indicates ow value printed on scale
(at 100 %)
89 SOFT_REVISION FW Version OctetString R/- e.g. V1.00 Indicates transmitter's rmware version

Questions and Answers: