TABLE 9: DNH060 COOLING CAPACITIES - 5 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
1,700 CFM 1,800 CFM 1,900 CFM 2,000 CFM 2,100 CFM
WB °FWB °FWB °FWB °FWB °F
72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57
85 °F
NET CAP.
MBH
66.863.158.257.068.264.459.458.269.565.660.659.369.365.460.359.169.065.160.158.9
TOTAL POWER
INPUT kW
5.06 4.96 5.02 4.83 5.13 5.03 5.10 4.90 5.21 5.11 5.17 4.97 5.33 5.24 5.30 5.09 5.46 5.36 5.43 5.22
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 42.8 53.5 58.2 57.0 44.6 55.8 59.4 58.2 46.5 58.1 60.6 59.3 47.8 59.5 60.3 59.1 49.1 61.0 60.1 58.9
83 37.9 48.7 57.7
57.0 39.4 50.6 59.1 58.2 41.0 52.5 60.6 59.3 41.9 53.6 60.3 59.1 42.9 54.8 60.1 58.9
8033.143.852.854.234.345.454.756.135.447.056.658.136.047.757.558.536.648.558.5
58.9
7728.239.048.049.429.140.249.550.929.941.451.152.530.141.851.652.630.342.352.252.6
7423.434.143.144.523.935.044.345.724.435.945.547.024.235.945.746.724.136.045.946.4
71 - 29.3 38.3 39.7 - 29.8 39.1 40.6 - 30.4 40.0 41.5 - 30.0 39.8 40.8 - 29.7 39.7 40.1
68 - 24.5 33.4 34.8 - 24.6 33.9 35.4 - 24.8 34.4 35.9 - 24.1 33.9 34.9 - 23.5 33.4 33.8
95 °F
NET CAP.
MBH
66.161.356.855.267.062.157.656.067.963.058.456.767.762.758.256.667.462.558.056.4
TOTAL POWER
INPUT kW
5.66 5.60 5.58 5.37 5.72 5.66 5.64 5.43 5.78 5.72 5.70 5.49 5.86 5.80 5.77 5.56 5.94 5.87 5.85 5.63
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 42.9 53.4 56.8 55.2 44.6 55.5 57.6 56.0 46.4 57.6 58.4 56.7 47.7 59.1 58.2 56.6 49.0 60.6 58.0 56.4
83 38.1 48.6 55.3
55.2 39.5 50.3 56.9 56.0 40.8 52.0 58.4 56.7 41.8 53.2 58.2 56.6 42.8 54.3 58.0 56.4
8033.243.750.551.734.345.152.153.435.346.553.755.035.947.354.655.736.548.155.5
56.4
7728.438.945.646.929.139.946.948.229.840.948.149.530.041.448.749.830.241.849.250.1
7423.534.040.842.123.934.741.743.024.235.442.643.924.135.542.843.924.035.543.043.8
71 - 29.2 35.9 37.2 - 29.5 36.5 37.8 - 29.9 37.1 38.4 - 29.6 36.9 38.0 - 29.3 36.7 37.6
68 - 24.3 31.1 32.4 - 24.3 31.3 32.6 - 24.3 31.5 32.9 - 23.7 31.0 32.1 - 23.0 30.5 31.3
105 °F
NET CAP.
MBH
62.557.153.051.763.558.053.852.664.558.954.653.464.258.654.353.163.858.254.052.8
TOTAL POWER
INPUT kW
6.29 6.17 6.12 6.02 6.36 6.24 6.19 6.09 6.43 6.31 6.26 6.16 6.55 6.43 6.38 6.27 6.68 6.55 6.50 6.39
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 41.8 51.8 53.0 51.7 43.6 54.0 53.8 52.6 45.5 56.2 54.6 53.4 47.1 56.7 54.3 56.1 48.7 57.3 54.0 52.8
83 36.9 47.0 52.2
51.7 38.4 48.9 53.4 52.6 39.9 50.7 54.6 53.4 41.2 52.3 54.3 53.1 42.5 53.8 54.0 52.8
8032.142.248.548.233.243.750.249.934.445.252.051.635.346.452.452.236.247.652.8
52.8
7727.337.343.643.328.138.545.044.728.939.646.446.129.440.546.546.329.941.346.546.5
7422.432.538.838.522.933.339.839.523.334.140.940.523.534.640.640.423.735.040.340.3
71 - 27.6 34.0 33.6 - 28.1 34.6 34.3 - 28.5 35.3 35.0 - 28.7 34.7 34.5 - 28.8 34.0 34.0
68 - 22.8 29.1 28.8 - 22.9 29.5 29.1 - 23.0 29.8 29.4 - 22.8 28.8 28.6 - 22.5 27.8 27.8
115 °F
NET CAP.
MBH
59.052.949.148.260.153.850.049.161.254.850.950.060.754.450.549.660.254.050.149.2
TOTAL POWER
INPUT kW
6.92 6.75 6.67 6.67 7.00 6.83 6.75 6.75 7.08 6.90 6.82 6.82 7.25 7.07 6.99 6.99 7.41 7.23 7.15 7.15
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 40.7 50.3 49.1 48.2 42.6 52.6 50.0 49.1 44.6 54.8 50.9 50.0 46.5 54.4 50.5 49.6 48.4 54.0 50.1 49.2
83 35.8 45.4
49.1 48.2 37.4 37.4 50.0 49.1 39.0 49.4 50.9 50.0 40.6 51.3 50.5 49.6 42.2 53.3 50.1 49.2
8031.040.646.544.632.242.248.446.433.543.850.248.234.745.450.248.735.947.0
50.1 49.2
7726.135.741.739.827.037.043.241.227.938.344.742.628.839.544.342.829.740.843.843.0
7421.330.936.834.921.831.838.036.022.432.839.237.122.933.638.436.923.434.537.636.7
71 - 26.0 32.0 30.1 - 26.6 32.8 30.8 - 27.2 33.6 31.6 - 27.7 32.5 31.0 - 28.3 31.3 30.5
68 - 21.2 27.1 25.2 - 21.4 27.6 25.6 - 21.7 28.1 26.0 - 21.8 26.6 25.1 - 22.0 25.1 24.2
125 °F
NET CAP.
MBH
55.548.745.244.756.749.746.245.757.950.847.246.757.350.246.746.256.749.746.245.7
TOTAL POWER
INPUT kW
7.50 7.30 7.20 7.30 7.60 7.40 7.30 7.40 7.70 7.50 7.40 7.50 7.90 7.70 7.60 7.70 8.20 7.90 7.80 7.90
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 39.6 48.7 45.2 44.7 41.6 51.1 46.2 45.7 43.6 53.5 47.2 46.7 45.9 52.0 46.7 46.2 48.1 50.6 46.2 45.7
83 34.7 43.9
46.0 44.7 36.4 46.0 46.6 45.7 38.1 48.1 47.2 46.7 40.0 50.4 46.7 46.2 41.9 52.8 46.2 45.7
8029.939.044.541.031.240.846.542.932.642.548.544.834.144.548.045.235.646.547.4
45.7
7725.034.239.736.226.035.641.337.727.037.043.039.228.238.642.139.329.440.341.139.4
7420.229.334.831.320.830.436.132.521.531.437.433.722.332.736.233.423.134.034.933.1
71 - 24.5 30.0 26.5 - 25.2 30.9 27.3 - 25.9 31.9 28.2 - 26.8 30.3 27.5 - 27.7 28.6 26.9
68 - 19.6 25.1 21.7 - 20.0 25.7 22.1 - 20.4 26.4 22.6 - 20.9 24.4 21.6 - 21.5 22.4 20.6
1.
These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY