FORM 100.50-NOM7 (808)
71
JOHNSON CONTROLS
6
The controller will wait 30 seconds from the time of the 
above control actions and then restart the Supply Fan 
by setting the Supply Fan output to ON (high). Normal 
heating or cooling operation will begin.
VFD Bypass operation will continue until the VFD By-
pass input goes low (0 volts). The unit will then return 
to normal operation.
ANALOG INPUT OPERATION
This section describes the control operation of the (13) 
thirteen analog inputs. These inputs will be used by the 
control to monitor and respond to unit temperatures, 
pressures, enthalpy, etc. The connection “layout” for the 
IO (inputs/outputs) is shown in the MOD-DCU connec-
tion map in Figure 20. Notice that the gure shows the 
Jack connection designated by “J”, and the pin number 
located on the inside of the board diagram. The input 
or output designations are shown on the outside of the 
gure. For example, J11 – 1 is jack eleven - pin 1 and 
is AI5 (analog input 5). J13 – 3 is jack 13 - pin 3 and is 
AI14 (analog input 14). For example, AI5 (J11 – 1) is the 
input for Outside Air Relative Humidity, and is used as 
part of the economizer control scheme. AI13 (J13 – 1) 
is the input for Supply Air Temperature, and is used for 
control in both the CV and VAV control schemes. The 
analog inputs are also in the I/O tables in Table 17 with 
descriptions for each input.
Return, Outside, Supply Air and Slab  
Temperature
The temperature sensors are RTD sensors that can be 
checked with an ohmmeter. Table 8 provides the resis-
tance values for a given temperature in °F.
Duct Pressure Transducer
The duct pressure transducer is mounted in the return air 
section of the unit on the panel wall. The purpose of this 
transducer is to sense and convert the static pressure in the 
supply-side of the duct to a DC voltage. The DC voltage 
is then sent to the unit controller and compare against the 
Duct Static Pressure setpoint. The control wiring is fac-
tory wired, but pneumatic tubing must be eld supplied 
and installed (refer to Installation section in manual). 
The duct pressure transducer measures dierential pres-
sure between the pressure in the duct and atmospheric 
pressure. When verifying transducer operation, the 
technician must insert a tee into the pneumatic tubing 
to connect a manometer and verify the pressure being 
applied to the transducer. Once this pressure is known, 
a comparison can be made of the duct pressure vs. out-
put volts DC from the transducer. Table 11 shows the 
relationship between the pressure applied to the duct 
pressure transducer and the output voltage.
Building Pressure Transducer
The building pressure transducer is located in the return 
air section of the unit. The purpose of this transducer is 
to sense and convert the static pressure in the building 
to a DC voltage. The DC voltage is then sent to the unit 
controller and compare against the Building Pressure 
setpoint. The control wiring from the transducer is fac-
tory wired, but pneumatic tubing must be eld supplied 
and installed (refer to Installation section in manual). 
The building pressure transducer measures dierential 
pressure between the pressure in the building and at-
mospheric pressure. When verifying transducer opera-
TABLE  8  –   TEMPERATURE SENSOR RESISTANCE 
TABLE
TEMPERATURE SENSOR OUTPUT TABLE
 TEMP. OHMS TEMP. OHMS
 °F RESISTANCE °F RESISTANCE
 -20  751  80  1030
 -10  777  90  1060
 0  803  100  1090
 10  830  110  1121
 20  858  120  1152
 30  885  130  1184
 40  914  140  1216
 50  942  150  1248
 60  971  160  1281
 70  1000 170 1314
TABLE 9 –  *DUCT PRESSURE TRANSDUCER 
OUTPUT TABLE
DUCT PRESSURE TRANSDUCER OUTPUT TABLE
  DIFFERENTIAL INPUT  OUTPUT VOLTAGE
  PRESSURE - IWG  - VDC
 0.5  0.25  0.5
 1.0  0.50  1.0
 1.5  0.75  1.5
 2.0  1.00  2.0
 2.5  1.25  2.5
 3.0  1.50  3.0
 3.5  1.75  3.5
 4.0  2.00  4.0
 4.5  2.25  4.5
 5.0  2.50  5.0
* 2.5 IWC Duct Transducer Available for FlexSys Option