TABLE 5 – HISTORY FUNCTION TEXT (LINE 2)
TABLE 6 HISTORY POINTS DATA LIST
DISPLAY TEXT DISPLAY TEXT
Tstat Input= Y2 (Y1,W1,W2,N/A) Supply Fan= On (Off)
Occ Input= OCC (UNOCC) Sfan Output= XXX% (N/A)
G Input= On (Off) Exhaust Fan= On (Off, N/A)
Space Temp= XX.X
o
F (N/A) Efan Output= XXX% (N/A)
Space Tmp SP= XX.X
o
F (N/A) Comp 1-A= On (Off, N/A, L/O)
SA Temp= XX.X
o
F (N/A) Comp 1-B= On (Off, N/A, L/O)
SATempSP= XX.X
o
F (N/A) Comp 2-A= On (Off, N/A, L/O)
RA Temp= XX.X F (N/A) Comp 2-B= On (Off, N/A, L/O)
RA RH= XXX% (N/A) Comp 3-A= On (Off, N/A, L/O)
3
RA Enth= XX.X btu/lb (N/A) Comp 3-B= On (Off, N/A, L/O)
3
OA Temp= XX.X
o
F Ht Steps ON= XX (N/A)
OA RH= XXX % (N/A) Ht Steps Avail= X (N/A)
OA Enth= XX.X btu/lb (N/A) Ht Valve Out= XXX % (N/A)
Duct Press= X.XX inwg (N/A) OA Damper Pos= XXX % (N/A)
Duct Pr SP= X.XX inwg (N/A) SAT SP= XXX
o
F (N/A)
Bldg Pr= X.XX inwg (N/A)
Bldg Pr SP= X.XX inwg (N/A)
1
Conditions dependent, see the Fault Description Table in Service Section of Manual.
2
No error history is recorded; RDU displays Trouble condition.
3
Not used on R410A units
4
Not used on Millenniums.
Error Text (Line 2) Classication (Line 3) Error Text (Line 2) Classication (Line 3)
COR Status Fault Alarm F/RH Sensor Fault Trouble
Duct Sensor Fault Alarm F/Slab Sensor Fault Trouble
Excess Duct Pressure Alarm Heat SAT Fault Trouble
HW Freeze Fault Alarm IAQ Sensor Fault Trouble
MSAT Sensor Fault Alarm OA Flow Sensor Fault Trouble
SAT Sensor Fault Alarm
1
OAH Sensor Fault Trouble
Supply Fan Fault Alarm
OAH Sensor Fault Trouble
Sys1 Sfty Lckout #1 Alarm RA Byp Filter Fault Trouble
Sys1 Sfty Lckout #2 Alarm RAH Sensor Fault Trouble
Sys2 Sfty Lckout #1 Alarm RAT Sensor Fault Trouble
1
Sys2 Sfty Lckout #2 Alarm SensConsist Fault 1 Trouble
Sys3 Sfty Lckout #1
3
Alarm SensConsist Fault 2 Trouble
Sys3 Sfty Lckout #2
3
Alarm Space Control Fault Trouble
Thermostat Conflict Alarm Space Sensor Fault Trouble
Sys1 Safety Trip Trouble
Air Switch Fault Trouble Sys2 Safety Trip Trouble
Bad OAF Transducer Trouble Sys3 Safety Trip
3
Trouble
Cooling SAT Fault Trouble Tstat Cooling Fault Trouble
2
DischargePress Fault Trouble Tstat Heating Fault Trouble
2
Evap Freeze Fault
4
Trouble
1
Unit Filter Fault Trouble
Excess Cooling Fault Trouble
UNT Comm Fault Trouble
Excess Heating Fault Trouble