Parameter Descriptions and Options
TABLE 7 – SETPOINTS AND VALUES
Continued on next page
DESCRIPTION TEXT ON OCC UNITS
DEFAULT VALUE OCC
VALUE RANGE KEY
1. Unit Type CV CV, VAV, MIT-VAV Conguration
2. Dirty Filter Switch OFF ON or OFF Conguration
3. ASCD Override OFF ON or OFF Conguration
4. Run Test OFF ON or OFF Conguration
5. Panel Test OFF ON or OFF Conguration
6. # of Compressors 4 4 or 6 Conguration
7. # of Heat Steps 0 0-6
2
Conguration
8. Heating Type
1
None, Gas
None, Gas, Electric,
Conguration
HW, or Steam
9. Freezestat OFF ON or OFF Conguration
10. Transducer Package 0 0 – 3 Conguration
11. Reset Lead-Lag OFF ON or OFF Conguration
12. Cooling SAT Limit #1 °F 45°F 40°-50°F Conguration
13. Cooling SAT Limit #2 °F 50°F 40°-65°F Conguration
14. Heating SAT Limit °F 160°F 100°-195°F Conguration
15. Power Exhaust Cong 0 0 - 3 Conguration
16. Economizer Installed NO YES – NO Conguration
17. Duct Sensor Hi Limit inwg 5.0 2.5 – 5.0 Conguration
18. Sys X Comp Runtimes
2
starts 0 (> expected value) Service
19. Sys X Comp Starts
2
hr 0 (> expected value) Service
20. Exhaust (Fan Runtimes)
2
hr 0 (> expected value) Service
21. Unoccupied Heating °F 60° 45°-99° Setpoint
22. Unoccupied Cooling °F 85° 45°-99° Setpoint
23. Occupied Heating °F 68° 45°-99° Setpoint
24. Occupied Cooling °F 72° 45°-99° Setpoint
25. VAV Cool High Temp °F 60° 50°-70° Setpoint
26. VAV Cool Low Temp °F 55° 50°-70° Setpoint
27. VAV Cool Reset Temp °F 72° 60°-95° Setpoint
28. Duct Static Pressure inwg 1.50 0.00-5.00 Setpoint
29. Building Pressure inwg +0.100 -0.200-+0.200 Setpoint
30. Economizer 1st Stage °F 55° 40°-65° Setpoint
31. Economizer 2nd Stage °F 50° 40°-65° Setpoint
32. SAT Econo Load Heat °F 150 100 – 195 Setpoint
33. Outside Air Enthalpy btu/lb 28 22-40 Setpoint
34. Cmfrt Vent High SAT °F 80° 60°-85° Setpoint
35. Cmfrt Vent Low SAT °F 70° 60°-85° Setpoint
36. Warm-Up RAT °F 70° 50°-85° Setpoint
37. Hydro Heat 1st Stage °F 100° 75°-150° Setpoint
38. Hydro Heat 2nd Stage °F 115° 75°-150° Setpoint
39. OA Damper Min Pos #1 % 15% 0-100% Setpoint
40. OA Damper Min Pos #2 % 30% 0-100% Setpoint
41. Demand Ventilation ppm 1000 750-1500 Setpoint
42. (FlexSys) MSAT Setpoint °F 62 55 – 70 Setpoint
43. (FlexSys) Min Dewpt Di󰀨 °F 3 1 – 5 Setpoint
44. Language Option English English, Spanish Unit Setup
45. Measurement Units Imperial Imperial, SI Canada, SI Unit Setup
46. Space Sensor Enable OFF ON or OFF Unit Setup
47. Unocc Override Time min 60 min 0-240 min Unit Setup
48. Space Setpt O󰀨set °F 3°F 0°-5°F Unit Setup
49. Fan ON With Sensor ON ON or OFF Unit Setup
50. RAT Sensor Enable OFF ON or OFF Unit Setup
51. Space Temp Alrm Di󰀨 °F 5°F 0°-25°F Unit Setup
52. Space Temp Alrm Time min 60 min 0-120 min Unit Setup
53. Sens Consist Enable OFF ON or OFF Unit Setup
54. SAT Control For Cool ON ON or OFF Unit Setup
55. SAT Control For Heat °F OFF ON or OFF Unit Setup
56. Rev Act Heat Valve OFF ON or OFF Unit Setup