FORM 100.50-NOM7 (808)
27
JOHNSON CONTROLS
3
Morning Warm Up
Morning Warm Up operation is carried out when:
The Morning Warm Up parameter is ON.
The Internal Clock/Schedule parameter is ON.
Occupancy is scheduled for the current day.
The Morning Warm Up start time will be 60 minutes
prior to scheduled occupancy, or BAS initiates the
morning warm-up.
When started, the Morning Warm Up operation is as
follows:
Close economizer.
Turn the Supply Fan ON and operate for 5 minutes
before beginning temperature control.
For stepped heating:
Control to maintain the RAT to the Morning
Warm Up Setpoint using the algorithm illus-
trated in Figure 12.
For Hydronic heating:
The SAT is controlled to the 2
nd
Stage Hydronic
Heat Setpoint.
The VAV Relay output of the controller is set to
10 VAC during heating.
Morning Warm Up operation will end when:
An occupancy (space is occupied) input is received
from the controller input.
The scheduled occupancy time occurs.
The Morning Warm Up operation times out based
on the Max Morning Warm Up Time parameter.
The transition from cooling to occupied heating
occurs at 2°F below the “VAV Setpoint for SAT
reset”.
The reverse transition at 1.5°F below the “VAV
Setpoint for SAT reset”. There is no “satised” or
“idle” state of the unit between cooling and oc-
cupied heating.
FIG. 12 OCCUPIED HEATING AND COOLING
SETPOINT SELECTION ALGORITHM
Enable VAV
Low Te mp.
Setpoint For
Cooling
Enable VAV
High Temp.
Setpoint For
Cooling
Enable VAV
Occupied
Hearing (If
Allowed)
-2.0˚F -1.5˚F
-0.5˚F
VAV Setpoint
For SAT Reset
+2.0F
SPA CE TEMPERA TURE
LD06561