FORM 100.50-NOM7 (808)
27
JOHNSON CONTROLS
3
Morning Warm Up
Morning Warm Up operation is carried out when:
 •  The Morning Warm Up parameter is ON.
 •  The Internal Clock/Schedule parameter is ON.
  •  Occupancy is scheduled for the current day.
The Morning Warm Up start time will be 60 minutes 
prior to scheduled occupancy, or BAS initiates the 
morning warm-up.
When started, the Morning Warm Up operation is as 
follows:
  •  Close economizer.
  •  Turn the Supply Fan ON and operate for 5 minutes 
before beginning temperature control.
  •  For stepped heating:
    •  Control to maintain the RAT to the Morning 
Warm Up Setpoint using the algorithm illus-
trated in Figure 12.
  •  For Hydronic heating:
    •  The SAT is controlled to the 2
nd
 Stage Hydronic 
Heat Setpoint.
    •  The VAV Relay output of the controller is set to 
10 VAC during heating.
Morning Warm Up operation will end when:
  •  An occupancy (space is occupied) input is received 
from the controller input.
  •  The scheduled occupancy time occurs.
  •  The Morning Warm Up operation times out based 
on the Max Morning Warm Up Time parameter.
 •  The transition from cooling to occupied heating  
occurs at 2°F below the “VAV Setpoint for SAT 
reset”.
 •  The reverse transition at 1.5°F below the “VAV 
Setpoint for SAT reset”. There is no “satised” or 
“idle” state of the unit between cooling and oc-
cupied heating.
FIG. 12 –  OCCUPIED HEATING AND COOLING 
SETPOINT SELECTION ALGORITHM
Enable VAV
Low Te mp.
Setpoint For
Cooling
Enable VAV
High Temp.
Setpoint For
Cooling
Enable VAV
Occupied
Hearing (If
Allowed)
-2.0˚F -1.5˚F
-0.5˚F
VAV  Setpoint
For SAT Reset
+2.0F
SPA CE TEMPERA TURE
LD06561