FORM 100.50-NOM7 (808)
9
JOHNSON CONTROLS
1
GENERAL
The OptiLogic
TM
 control center is a fully-integrated fac-
tory-packaged control and includes a display unit with 
a 4x20 character LCD display. OptiLogic
TM
 continually 
monitors all control setpoints and congurations. If a 
unit or control component or sensor fails, the controller 
noties the user of a problem. If desired, YORK ser-
vice can provide remote monitoring and automatically 
schedule a service technician to make the repair and 
maintain your comfort.
All control points within the unit are factory-installed, 
wired and tested. The OptiLogic
TM
 controls can com-
municate with BACNet IP or MSTP, or Lonworks (see 
UPG M letter M-84-2007).
A eld installed optional lter maintenance alarm indi-
cates when a lter becomes dirty and requires replace-
ment or cleaning.
FIELD WIRING
Figure 1 shows the eld control wiring to CTB3 for both 
a Constant Volume and Variable Air Volume units. All 
eld control wiring is eld supplied and installed. 
Thermostat
The thermostat (if used) can be used for either CV or 
VAV units. When used, the thermostat is the primary 
means of control for the unit. The thermostat should be 
mounted on an inside wall approximately 56" above the 
oor where it will not be subject to drafts, sun exposure 
or heat from electrical xtures or appliances.
Space Sensor
The space sensor (if used) can be used on either CV or 
VAV units. The space sensor can be used for unit control 
in lieu of a thermostat. Even if a thermostat is wired 
to the rooftop unit, the space sensor will supply space 
air temperature values if connected.  When mounting 
a space sensor, it should be located on an inside wall 
approximately 56" above the oor where it will not be 
subject to drafts, sun exposure or heat from electrical 
xtures or  appliances. Shielded Wire must be used 
that is grounded at control panel only. 
Note that 24 volts (R), terminal 16, must be used as the 
24 volt AC source for switching the contact to the unit 
controller shutdown input. Use of any power source 
SECTION 1 – INSTALLATION
external to the controller will result in damage to the 
unit controller.
CO
2
 Sensor
The optional CO
2
 sensor is used for demand ventilation 
and must be wired to the eld control wiring terminal 
block using three-conductor shield wire.  Shielded wire, 
grounded at the control box only, must be used.
Occupied/Unoccupied Input
A contact-closure input is provided for hard-wiring an 
external device such as a central time clock, a thermostat 
with scheduling or BAS system, or a manual switch.
  Contact Closure = Occupied 
  Contacts Open = Unoccupied
Note that 24 volts (R), terminal 16, must be used as 
the 24 volt AC source for switching the contact to the 
unit controller Occupied/Unoccupied input. Use of any 
power source external to the controller will result in 
damage to the unit controller.
Shutdown Input
A contact-closure input is provided for emergency 
shutdown of the unit. When a contact closure to this 
input, the unit shuts down with supply fan, exhaust fan 
turned o,  and  outside air dampers  are  closed.  This 
state is maintained until the input is deactivated (con-
tacts open).
  Contact Closed = Shutdown
  Contacts Open = Normal Operation
Note that 24 volts (R), terminal 16, must be used as the 
24 volt AC source for switching the contact to the unit 
controller shutdown input. Use of any power source 
external to the controller will result in damage to the 
unit controller.
Smoke Purge Input
A contact-closure input is provided for a smoke purge 
sequence. When a contact-closure occurs at this input, 
one of ve purge sequences will be initiated, depending 
on unit programming. This input will cause a specic 
operation of supply fan, exhaust fans, return dampers, 
outside  air  dampers,  and  exhaust  dampers.  The  ve 
possible smoke purge modes (Shutdown, Pressurization, 
Exhaust, Purge, and Purge with Duct Pressure Control) 
are described in the controls section of this manual.