FORM 100.50-NOM7 (808)
31
JOHNSON CONTROLS
3
100%
80%
60%
40%
20%
0%
0%
50%
100%
OUTPUT TO VFD
OAD MINIMUM  POSITION
2
4
3
1
Note: 
   For  units  congured  for  Constant  Volume  Operation,  the  OAD 
Min Position #2 setting will be ignored and only OAD Min Position 
#1 will be used to set the Minimum Position of the outside air 
damper. 
FIG. 13 – OAD MINIMUM POSITION RESET
LD06562
    OAD MIN.  OAD MIN.
 
CURVE
  POSITION #1  POSITION #2
  1  10%
  2 
25%
 25%
  3  50%
  4  80%
Demand Ventilation
Demand Ventilation is a control sequence that can in-
crease or decrease the amount of ventilation introduced 
to the building based on ventilation demand. The de-
mand for ventilation will be determined by comparing 
the level of CO
2
 in the building to the Demand Venti-
lation Setpoint. The CO
2
 level in the building will be 
measured by an appropriate CO
2
 sensor connected to 
the unit.
The Demand Ventilation control sequence will only be 
allowed to function if:
 •  The IAQ Sensor Enable setting is set to ON.
  •  The unit is equipped with an economizer and Econ-
omizer Enable = ON.
 •  The Airow Meas Cong conguration is = 0 or 1 
(Minimum or 1/4-3/4 congurations not installed 
or not enabled). 
  •  Occupancy status is = Occupied.
Demand Ventilation control will operate in both heating 
and cooling modes and will increase the position of the 
economizer (OA Damper) from the minimum position 
or the control positions of economizer or economizer 
loading as required to meet the Demand  Ventilation 
Setpoint.
Sensor
If all conditions are met, the control will look for an 
attached CO
2
 sensor at the appropriate AI. The reading 
at the AI will be used along with the IAQ Sensor Span 
setting to determine the building CO
2
 level.
If the CO
2
 level indicated at the AI is out of range, the 
controller will interpret the reading as a sensor failure 
and generate a Trouble Fault. Demand Ventilation con-
trol sequences will not be allowed if the CO
2
 sensor is 
determined to be unreliable.
Algorithm
An appropriate algorithm will be used for Demand 
Ventilation control. A step and wait algorithm with the 
following characteristics is preferred:
  •  Step  size  is a  function of  the  dierence between 
the measured IAQ (CO2) level and the Demand 
Ventilation Setpoint.
  •  Step time is xed.
The Demand Ventilation operation will have the fol-
lowing constraints:
The maximum OA Damper position for the Demand 
Ventilation operation will be equal to the (MAX DV 
MultiplIer) * (OA Damper Min Pos #1).