JOHNSON CONTROLS
42
FORM 100.50-NOM7 (808)
Menu Navigation and Display Descriptions
The Operation Data key (or Menu Item) will move the
display to the rst display item of the Operation Data
group. The Operation Data group of display items will
give the user access to the units’ current operating pa-
rameters. The Operation Data group of display items
will be view only and will require no password.
Starting with the rst display item, the Operation Data
display items will be as follows:
“OPERATION DATA NAVIGATION
** OPERATION DATA **
RA Temp = 69.6°F
RA RH = 55%
RA Enth =26.0 btu/lb
** OPERATION DATA **
Supply Air Temp
Temp = 57.6°F
Setpt = 58.0°F
** OPERATION DATA **
Supply Duct Pressure
Press = 1.48 inwg
Setpt = 1.50 inwg
** OPERATION DATA **
Sys 1 Compressors
Comp A = ON
Comp B = OFF
** OPERATION DATA **
Sys 1 Compressors
Suc Press = 100 psig
Dis Press = 325 psig
** OPERATION DATA **
Compressor Staging
Next ON = 2-B
Next OFF = Waiting
** OPERATION DATA **
OA Temp = 73.4°F
OA RH = 48%
OA Enth =26.8 btu/lb
Line 2 Sys X Compressors
Line 3 Comp A = ON (OFF, FAULT, N/A)
Line 4 Comp B = ON (OFF, FAULT, N/A)
Line 2 Sys X Compressors
Line 3 Suc Press = XXX PSIG (N/A)
Line 4 Dis Press = XXX PSIG (N/A)
Line 2 Compressor Staging
Line 3 Next ON = X-X (N/A)
Line 4 Next OFF = X-X (N/A)
Line 2 OA Temp= XXX°F (0.0, ???)
Line 3 OA RH = XXX% (0.0, ???)
Line 4 OA Enth= XX.X btu/lb (0.0)
Line 2 RA Temp= XXX°F (0.0, ???)
Line 3 RA RH = XXX% (0.0, ???)
Line 4 RA Enth= XX.X btu/lb (0.0)
Line 2 Supply Air Temp
Line 3 Temp = XXX.X°F (0.0, ???)
Line 4 Setpt = XXX.X°F
Line 2 Supply Duct Pressure
Line 3 Press = X.XX inwg (0.0, ???)
Line 4 Setpt = X.XX inwg (0.0, ???)