Unit Sequence of Operation
VARIABLE AIR VOLUME
SEQUENCE OF OPERATION
Under Variable Air Volume Operation, the unit will be
controlled from one of two sources:
7-Wire Thermostat
Space Sensor
In addition to the two control methods, a VAV con-
gured unit can also operate “stand-alone” with the only
direct control being the Occupied/Unoccupied signal.
The method of control is as selected as described in the
following sections.
VAV Operation With a Thermostat
When VAV with Thermostat parameter is set to ON, a
Thermostat is used for SAT control.
VAV Operation With a Space Sensor
A Space Sensor is used for control when:
The VAV with Thermostat parameter is OFF, and
A Space Sensor is available.
If a Space Sensor is not available, the controller will
self-congure to Standalone VAV operation.
Standalone VAV Operation
Standalone VAV operation is used by the control
when:
The VAV with Thermostat parameter is OFF, and
No Space Sensor is available.
VAV Operating Modes
VAV operating modes have the following common
functions:
For heating, the Heating Mode Enable parameter
must be ON.
The VAV Heat Relay binary output is used to fully
open the VAV boxes when heating is ON.
For cooling, the Cooling Mode Enable parameter
must be ON.
Cooling (compressor) stages are controlled as
described in the following sections.
The SAT control algorithm for cooling is de-
scribed in the following sections.
The Supply Fan is:
Controlled as described in the Fan.
100 % ON when heating is ON.
Controlled to maintain the Duct Static Pressure
setpoint when cooling is ON.
ON and controlled for heating or cooling when
the Thermostat G output is ON.
Ramped up to its operation condition using
its variable output control when turned ON.
OFF when heating or cooling is OFF and oc-
cupancy is UNOCCUPIED.
An occupancy input is provided by the Ther-
mostat or Space Sensor.
For Economizer Operation, the Economizer
Installed parameter must be ON and the Econo-
mizer Enable parameter must be ON. The econ-
omizer is:
Closed for all unoccupied heating.
At the minimum position for occupied heat-
ing.
At minimum for occupied cooling when econ-
omizer is not available.
Closed for unoccupied cooling when econo-
mizer is not available.
At the economizer algorithm determined po-
sition for cooling with economizer available.
Unoccupied Heating With A Thermostat
The heating control is as described for “Occupied
Heating With A Thermostat” and the general operating
conditions.
Occupied Cooling With A Thermostat
The thermostat Y1 and Y2 outputs control SAT to:
Y1 = OFF, Y2 = OFF – No cooling
Y1 = ON, Y2 = OFF - Cooling to SAT setpoint
VAV High Temperature Setpoint for Cooling
Y1 = ON, Y2 = ON - Cooling to SAT setpoint
VAV Low Temperature Setpoint for Cooling
Y1 = OFF, Y2 = ON - Cooling to SAT setpoint
VAV Low Temperature Setpoint for Cooling
Unoccupied Cooling With A Thermostat
The cooling control is as described for Occupied
Cooling With A Thermostat and the general operating
conditions.
Occupied Heating With A Space Sensor
The programmable parameter VAV Operation with
Thermostat must be set to OFF and Space Sensor
signal must be reliable.