Parameter Descriptions and Options
Purge Schedule 
This is the programmable time of day to start Purge 
for each day.
Purge OAT High Limit
This programmable temperature is the upper limit for 
Purge using 100% outdoor air. 
Purge OAT Low Limit
This programmable temperature is the lower limit for 
Purge using 100% outdoor air.
Smoke Purge Mode
The smoke purge setting enables/disables the Smoke 
Purge function and tells the control what Smoke Purge 
control sequence to follow. The setting range is 0 – 5. A 
“0” setting tells the control to ignore the Smoke Purge 
input and do nothing (Smoke Purge disabled). A setting 
of 1 – 5 tells the control which one of ve smoke purge 
control sequences to follow when the Smoke Purge 
input is active. Smoke Purge conguration options are 
detailed in the section on Sequence Operation.
Internal Clk/Sched
This setting tells the control to use the Internal Time 
Clock and Schedule built into the controller for all 
scheduling functions. When this function is set to ON, 
all Occupied/Unoccupied commands and Morning 
Warm Up commands received over a Network (BAS) 
will be ignored. Unoccupied Override commands via 
Space Sensors and the hard wired Occupied/Unoccupied 
input will take priority over the internal scheduling.
Weekly Schedule
The schedule for time programmed operation of the 
unit is entered for all days of the week plus a holiday 
schedule. One start and stop time is allowed.
Holiday Schedule
Holiday dates are entered into the Holiday Schedule for 
use in time programmed operation. Up to 16 dates are 
allowed. Dates are assumed to be for the current year.
CONFIGURATION KEY PARAMETERS
These setpoints are intended to be programmed 
at the factory  and  should  not be changed by  eld 
personnel.
Unit Type
This tells the control that it is controlling one of the 
three selectable rooftop unit type options:
  •  Constant Volume
  •  Variable Air Volume
Dirty Filter Switch
This conguration setting tells the control that a Dirty 
Filter Switch is installed and that the control is to 
monitor the Dirty Filter Switch input and respond as 
specied to the input status.
ASCD Override
This is not an option parameter but rather a one-time 
command issued on the OptiLogic Control Center. 
When this command is issued, the control will read all 
compressor Anti Short Cycle Delays. If any of them are 
loaded with more than 30 seconds, the control will load 
30 seconds in them.
Number of Compressors 
This conguration setting tells the control the number 
of compressors available. There are two options, 4 
compressors and 6 compressors. All Models J32, J33 & 
J34 are set to four compressors.  Refer to the "Compres-
sor Staging" section for details on how the unit stages 
compressors.
Number of Heat Steps 
This conguration setting tells the control the number 
of heating steps (stages) available. This option will be 
selectable from 0 to 6. Note, zero (0) must be selected 
if hydronic heat is enabled.
Freezestat
This  conguration  setting  tells  the  control  that  a  hot 
water freeze protection Freezestat is installed on the unit 
and the control will monitor the hot water Freezestat 
input. This option is used only on units with hydronic 
heat (Hydronic Heat option is turned ON).
Reset Lead Lag
Setting Reset Lead Lag to ON tells the control to set the 
accumulated compressor run times to zero. This causes 
all compressors to be considered as if they have no run-
time history. This is a one time action. The control resets 
the ON to OFF as soon as the runtimes are zeroed.