10 Unitary Products Group
TABLE 7: COOLING CAPACITIES - 5 TON (DEE / DEG060)
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
95°F
TOTAL
CAP.
1
MBH
POWER
INPUT
2
kW
SENSIBLE CAPACITY
1
, MBH
TOTAL
CAP
.1
MBH
POWER
INPUT
2
kW.
SENSIBLE CAPACITY
1
, MBH
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
CFM
WB
°F
86 83 80 77 74 71 68 86 83
80 77 74 71 68
2500
72 75 4.6 53 46 38 31 23 - - 73 5.0 53 46 38 31 23 - -
67 67 4.5 64 56 49 41 34 26 19 65 4.9 64 56 49 41 34 26 19
62 62 4.5
62 62 62 54 47 39 32 60 4.9 60 60 60 53 46 38 31
57 56 4.4
56 56 56 48 41 33 26 55 4.8 55 55 55 47 40 32 25
2250
72 74 4.6 51 44 37 31 24 - - 72 5.0 50 43 37 30 23 - -
67 67 4.5 62 55 48 42 35 28 21 64 5.0 61 54 47 41 34 27 20
62 61 4.5
61 61 61 54 47 40 34 59 4.9 59 59 59 52 45 38 32
57 55 4.4
55 55 55 48 41 35 28 53 4.8 53 53 53 46 39 33 26
2000
72 73 4.5 49 43 37 31 25 - - 70 5.0 47 41 35 29 23 - -
67 66 4.5 60544842363024 63 5.0 58 52 46 40 34 28 22
62 60 4.4
60 60 60 54 48 42 36 58 4.9 58 58 57 51 45 39 33
57 55 4.4
55 55 54 48 42 36 30 52 4.8 52 52 61 45 39 33 27
1750
72 72 4.5 45 40 34 29 24 - - 68 5.0 43 38 33 27 22 - -
67 65 4.5 55 50 44 39 34 29 23 61 4.9 53 47 42 37 32 26 21
62 60 4.4
60 59 56 50 45 40 35 56 4.9 56 56 53 48 42 27 32
57 54 4.4
54 53 50 45 40 34 29 50 4.8 50 50 48 42 37 32 27
1500
72 71 4.5 41 37 32 27 23 - - 66 5.0 40 35 30 26 21 - -
67 63 4.5 50 46 41 36 32 27 22 58 4.9 48 43 39 34 29 25 20
62 59 4.4
59 57 52 47 43 38 34 54 4.9 54 54 49 44 40 35 31
57 53 4.4
53 52 47 42 38 33 28 49 4.8 49 49 44 40 35 30 26
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F 115°F
TOTAL
CAP
.1
MBH
POWER
INPUT
2
kW.
SENSIBLE CAPACITY
1
, MBH
TOTAL
CAP
.1
MBH
POWER
INPUT
2
kW.
SENSIBLE CAPACITY
1
, MBH
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
CFM
WB
°F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
2500
72 66 5.5 51 44 36 29 21 - - 60 6.0 49 41 34 26 19 - -
67 59 5.5 58544639312416 53 6.0
53 51 43 36 28 21 13
62 55 5.4
55 55 55 47 40 32 25 49 5.9 49 49 49 42 34 27 19
57 49 5.4
49 49 49 42 35 27 20 44 5.9 44 44 44 37 29 22 15
2250
72 65 5.5 48 42 35 28 21 - - 58 6.0 46 40 33 26 20 - -
67 58 5.5 57524538312518 52 6.0
52 49 43 36 29 22 16
62 54 5.4
54 54 54 48 41 34 28 48 5.9 48 48 48 44 37 30 24
57 48 5.4
48 48 48 42 36 29 22 44 5.9 44 44 44 39 32 25 19
2000
72 63 5.5 45 39 33 28 22 - - 57 6.0 44 38 32 26 20 - -
67 58 5.5 55504438322620 52 6.0
52 48 42 36 30 24 18
62 52 5.4
52 52 52 48 42 36 30 47 5.9 47 47 47 46 40 34 28
57 47 5.4
47 47 47 43 37 31 25 43 5.9 43 43 43 41 35 29 23
1750
72 62 5.5 42 36 31 26 21 - - 55 6.1 40 35 30 24 19 - -
67 55 5.5 50 45 40 35 30 24 19 50 6.0 48 43 38 33 28 22 17
62 51 5.4
51 51 50 45 40 35 29 46 6.0 46 46 46 43 37 32 27
57 46 5.4
46 46 45 40 35 30 24 41 5.9 41 41 41 38 33 27 22
1500
72 60 5.5 38 33 29 24 19 - - 53 6.1 36 32 27 23 18 - -
67 53 5.5 46 41 37 32 27 23 18 47 6.1 44 39 35 30 25 21 16
62 49 5.4
49 49 47 42 37 33 28 44 6.0 44 44 44 39 35 30 25
57 44 5.4
44 44 42 37 33 28 23 40 6.0 40 40 40 35 30 26 21
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 10 or 11, multiply
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan
motor power input is 0.36kW. Refer to Tables 10 or 11 for the kW of the supply air blower motor.
NOMINAL RATING ALL SENSIBLE CAPACITY