036-21411-002-A-0204
20 Unitary Products Group
TABLE 21: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ BELT DRIVE DEE036 & 048
MODEL
DEE
POWER
SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
SUPPLY
AIR
BLOWER
MOTOR
FLA
ELECTRIC HEATERS
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE
1
AMPS
MAX.
SIZE
HACR
2
BREAKER
AMPS
kW STAGES
TOTAL
AMPS
036
208-1-60
2CE04500506
5.3
4.0 1 19.1 34.9 50 50
2CE04500706 5.6 1 27.1 44.6 50 50
2CE04501006 8.0 1 38.3 58.6 60 60
2CE04501506 11.9 2 57.4 82.5 90 90
2CE04502006 15.9 2 76.6 106.4 110 110
230-1-60
2CE04500506
5.3
5.3 1 22.1 38.4 50 50
2CE04500706 7.5 1 31.2 49.8 50 50
2CE04501006 10.6 1 44.2 66.0 70 70
2CE04501506 15.9 2 66.3 93.6 100 100
2CE04502006 21.2 2 88.3 121.2 125 125
208-3-60
2CE04500525
3
5.3
4.0 1 11.0 25.2 35 35
2CE04500725
3
5.6 1 15.6 26.2 35 35
2CE04501025 8.0 1 22.1 34.2 35 35
2CE04501525 11.9 2 33.1 48.1 50 50
2CE04502025 15.9 2 44.2 61.9 70 70
230-3-60
2CE04500525
3
5.3
5.3 1 12.7 25.2 35 35
2CE04500725
3
7.5 1 18.0 29.2 35 35
2CE04501025 10.6 1 25.5 38.5 40 40
2CE04501525 15.9 2 38.2 54.4 60 60
2CE04502025 21.2 2 51.0 70.4 80 80
460-3-60
2CE04500746
3
3.1
6.8 1 8.2 14.1 20 20
2CE04501046
3
10.1 1 12.1 19.1 20 20
2CE04501546
3
13.6 1 16.4 24.3 25 25
2CE04502046
3
19.5 2 23.5 33.2 35 35
575-3-60
2CE04501058
3.1
10.6 1 10.2 16.6 20 20
2CE04501558 15.9 1 15.3 23.0 25 25
2CE04502058 21.2 2 20.4 29.4 30 30
048
208-1-60
2CE04500506
8.6
4.0 1 19.1 42.2 60 60
2CE04500706 5.6 1 27.1 44.4 60 60
2CE04501006 8.0 1 38.3 58.8 60 60
2CE04501506 11.9 2 57.4 82.3 90 90
2CE04502006 15.9 2 76.6 106.3 110 110
230-1-60
2CE04500506
8.6
5.3 1 22.1 42.2 60 60
2CE04500706 7.5 1 31.2 49.8 60 60
2CE04501006 10.6 1 44.2 66.0 70 70
2CE04501506 15.9 2 66.3 93.6 100 100
2CE04502006 21.2 2 88.3 121.2 125 125
208-3-60
2CE04500525
3
5.2
4.0 1 11.0 25.9 40 40
2CE04500725
3
5.6 1 15.6 25.9 40 40
2CE04501025 8.0 1 22.1 34.3 40 40
2CE04501525 11.9 2 33.1 47.8 50 50
2CE04502025 15.9 2 44.2 61.7 70 70
230-3-60
2CE04500525
3
5.2
5.3 1 12.7 25.9 40 40
2CE04500725
3
7.5 1 18.0 29.1 40 40
2CE04501025 10.6 1 25.5 38.4 40 40
2CE04501525 15.9 2 38.2 54.3 60 60
2CE04502025 21.2 2 51.0 70.2 80 80
460-3-60
2CE04500746
3
2.6
6.8 1 8.2 13.6 20 20
2CE04501046
3
10.1 1 12.1 18.4 20 20
2CE04501546
3
13.6 1 16.4 23.7 25 25
2CE04502046
3
19.5 2 23.5 32.6 35 35
575-3-60
2CE04501058
2.0
10.6 1 10.2 15.2 20 20
2CE04501558 15.9 1 15.3 21.6 25 25
2CE04502058 21.2 2 20.4 28.0 30 30
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago) see Table 19 for
fuse block accessories available for field installation.