TABLE 20: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ DIRECT DRIVE DEE060
MODEL
DEE
POWER
SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
SUPPLY
AIR
BLOWER
MOTOR
FLA
ELECTRIC HEATERS
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE
1
AMPS
MAX.
SIZE
HACR
2
BREAKER
AMPS
kW STAGES
TOTAL
AMPS
060
208-1-60
2CE04500506
8.6
4.0 1 19.1 49.0 80 80
2CE04500706 5.6 1 27.1 49.0 80 80
2CE04501006 8.0 1 38.3 56.1 80 80
2CE04501506 11.9 2 57.4 80.0 90 90
2CE04502006 15.9 2 76.6 103.9 110 110
2CE04503006 22.2 2 106.9 141.9 150 150
230-1-60
2CE04500506
8.6
5.3 1 22.1 49.0 80 80
2CE04500706 7.5 1 31.3 49.0 80 80
2CE04501006 10.6 1 44.2 63.5 80 80
2CE04501506 15.9 2 66.3 91.1 100 100
2CE04502006 21.2 2 88.3 118.7 125 125
2CE04503006 29.6 2 123.3 162.4 175 175
208-3-60
2CE04500525
3
6.0
4.0 1 11.0 33.0 50 50
2CE04500725
3
5.6 1 15.6 33.0 50 50
2CE04501025 8.0 1 22.1 35.9 50 50
2CE04501525 11.9 2 33.1 49.7 50 50
2CE04502025 15.9 2 44.2 63.5 70 70
2CE04503025 22.2 2 61.7 85.4 90 90
230-3-60
2CE04500525
3
6.0
5.3 1 12.7 33.0 50 50
2CE04500725
3
7.5 1 18.0 33.0 50 50
2CE04501025 10.6 1 25.5 40.1 50 50
2CE04501525 15.9 2 38.2 56.1 60 60
2CE04502025 21.2 2 51.0 72.0 80 80
2CE04503025 29.6 2 71.2 97.3 100 100
460-3-60
2CE04500746
3
3.0
6.8 1 8.2 17.2 25 25
2CE04501046
3
10.1 1 12.1 19.3 25 25
2CE04501546
3
13.6 1 16.4 24.6 25 25
2CE04502046
3
19.5 2 23.5 33.4 35 35
2CE04503046
3
28.8 2 34.6 47.4 50 50
575-3-60
2CE04501058
2.4
10.6 1 10.2 16.9 20 20
2CE04501558 15.9 1 15.3 23.2 25 25
2CE04502058 21.2 2 20.4 29.6 30 30
2CE04503058 30.4 2 29.3 40.7 45 45
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), the following fuse
block accessories are available for field installation (see Table 19).