036-21411-002-A-0204
Unitary Products Group 7
TABLE 4: PHYSICAL DATA - BASIC UNIT
MODELS
DEE/DEG
036 048 060
EVAPORATOR
BLOWER
Centrifugal Blower (Dia. x Wd. in.)
Fan Motor HP (Direct - Drive)
Fan Motor HP (Belt - Drive)
12 x 10
1/2
1.5
12 x 10
3/4
1.5
12 x 10
1
1.5
EVAPORATOR
COIL
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.)
3
13
3.6
3
13
4.3
3
13
5.1
CONDENSER
FAN
Propeller Dia. (in.)
Fan Motor HP
Nom. CFM. Total
22
1/2
4,500
22
1/2
4,200
22
1/2
4,500
CONDENSER
COIL
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.)
2
18
17.1
2
18
17.1
2
18
17.1
AIR FILTERS
1
Quantity Per Unit (15” x 20” x 1”)
Quantity Per Unit (14” x 25” x 1”)
Total Face ARea (Sq. Ft.)
2
1
6.6
2
1
6.6
2
1
6.6
SYSTEM CHARGE Refrigerant 22 (Lbs./Oz.) 9/12 9/8 9/8
COMPRESSOR Quantity Per Unit: (Hermetic Type) 1 / Recpt 1 / Recpt 1 / Scroll
1.
Filter racks are adapted for 1” or 2” thick filters.