036-21411-002-A-0204
Unitary Products Group 15
TABLE 13: MOTOR AND DRIVE DATA - BELT-DRIVE BLOWER
MODEL
BLOWER
RANGE
RPM
MOTOR
1
ADJUSTABLE
MOTOR PULLEY
FIXED
BLOWER PULLEY
BELT
HP RPM
FRAME
SIZE
SERVICE
FACTOR
PITCH
DIA.
(in.)
BORE
(in.)
PITCH
DIA.
(in.)
BORE
(in.)
PITCH
LENGTH
(in.)
DESIG-
NATION
DEE / DEG 036 780 - 1120 1-1/2 1725 56 1.15 2.4-3.4 7/8 5.7 1 37.3 A36
DEE / DEG 048 790 - 1120 1-1/2 1725 56 1.15 2.4-3.4 7/8 5.7 1 37.3 A36
DEE / DEG 060 850 - 1220 1-1/2 1725 56 1.15 2.4-3.4 7/8 5.2 1 37.3 A36
1.
All motors have a solid base and are inherently protected. These motors can be selected to operate into their service fac-
tor because they are located in the moving air, upstream of any heating device.
TABLE 14: BASIC UNIT W/ DIRECT-DRIVE ELECTRICAL DATA
MODEL
DEE/
DEG
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
CON.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE
2
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
MIN MAX RLA LRA
036
208/230-1-60 187 253 16.7 87 2.3 4.4 27.5 40 40
208/230-3-60 187 253 13.1 110 2.3 4.4 23.1 35 35
460-3-60 414 504 6.7 54 1.4 2.2 12.0 15 15
575-3-60
3
518 630 5.1 44 1.4 2.2 10.7 15 -
048
208/230-1-60 187 253 18.7 135 2.3 5.0 38.6 60 60
208/230-3-60 187 253 11.9 130 2.3 5.0 25.7 40 40
460-3-60 414 504 6.3 64 1.4 2.2 13.2 20 20
575-3-60
3
518 630 4.9 52 1.4 2.2 11.4 15 -
060
208/230-1-60 187 253 32.1 169 2.3 6.6 49.0 80 80
208/230-3-60 187 253 19.3 123 2.3 6.6 33.0 50 50
460-3-60 414 504 10.0 62 1.4 3.3 17.2 25 25
575-3-60
3
518 630 7.9 50 1.4 3.3 14.6 20 -
1.
Rated in accordance with ARI Standard 110, utilization range “A”.
2.
Dual element, time delay type.
3.
DEE models only.