036-21411-002-A-0204
16 Unitary Products Group
TABLE 15: BASIC UNIT W/ BELT-DRIVE ELECTRICAL DATA
MODEL
DEE/
DEG
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
CON.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE
2
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
MIN MAX RLA LRA
036
208/230-1-60 187 253 16.7 87 2.3 7.6 30.1 45 45
208/230-3-60 187 253 13.1 110 2.3 5.3 23.9 35 35
460-3-60 414 504 6.7 54 1.4 2.6 12.4 20 20
575-3-60
3
518 630 5.1 44 1.4 2.0 9.8 15 15
048
208/230-1-60 187 253 18.7 135 2.3 8.6 42.6 60 60
208/230-3-60 187 253 11.9 130 2.3 5.2 26.3 40 40
460-3-60 414 504 6.3 64 1.4 2.6 14.3 20 20
575-3-60
3
518 630 4.9 52 1.4 2.0 11.4 15 15
060
208/230-1-60 187 253 32.1 169 2.3 8.6 51.0 80 80
208/230-3-60 187 253 19.3 123 2.3 6.0 32.4 50 50
460-3-60 414 504 10.0 62 1.4 3.0 16.9 25 25
575-3-60
3
518 630 7.9 50 1.4 2.4 13.7 20 20
1.
Rated in accordance with ARI Standard 110, utilization range “A”.
2.
Dual element, time delay type.
3.
= DEE models only.