JOHNSON CONTROLS
108
SECTION 7 - OPERATION
Form 201.47-ICOM1
Issue date: 17/11/2022
Table 17 - YVAA SC-EQ BAS Points List (cont'd)
YVAA / YVFA / YAGK SC-EQ BAS Points List
Rev 2.14
May 10, 2022
SC-EQ Software Version 4.5.0.18
Long Name
(BACnet Object Description)
Short Name
Notes
IP
SI
Object &
N2 Metasys
MODBUS
MODBUS
MODBUS
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Free Cooling Mode [0=M,1=Fc,2=Hy] FREE COOLING MODE
If Free Cooling Enabled
0=Mechanical, 1=Free Cooling,
2=Hybrid
MV12 N/A N/A N/A Unsigned N/A SNVT_count
Sys 1 System State SYS 1 SYSTEM STATE
0=Stopped, 1=Runing, 2=Faulted,
4=Locked Out, 5=Pre-Run
MV13 ADI 13 0132 X1 Unsigned N/A SNVT_count
Sys 2 System State SYS 2 SYSTEM STATE
0=Stopped, 1=Runing, 2=Faulted,
4=Locked Out, 5=Pre-Run
MV14 ADI 14 0133 X1 Unsigned N/A SNVT_count
Sys 1 System State AV SYS 1 SYSTEM STATE AV None None
0=Stopped, 1=Runing, 2=Faulted,
4=Locked Out, 5=Pre-Run
AV415 ADI 15 0134 X1 Unsigned nvoS1SysState SNVT_count
Sys 2 System State AV SYS 2 SYSTEM STATE AV None None
0=Stopped, 1=Runing, 2=Faulted,
4=Locked Out, 5=Pre-Run
AV416 ADI 16 0135 X1 Unsigned nvoS2SysState SNVT_count
Sys 1 Warning Code SYS 1 WARNING CODE None None
See Status Codes Tab
Sys 2 Warning Code SYS 2 WARNING CODE None None
See Status Codes Tab
AV419 ADI 19 0138 X1 Signed
AV420 ADI 20 0139 X1 Signed
AV73 ADF 73 0140 X1 Signed
Sys 1 Fan Kw SYS 1 FAN KW kW kW AV74 ADF 74 0141 X10 Unsigned nvoS1FankW SNVT_power_kilo
Sys 1 Compressor Kw SYS 1 COMPRESSOR KW kW kW AV75 ADF 75 0142 X10 Unsigned nvoS1CompkW SNVT_power_kilo
Sys 2 Fan Kw SYS 2 FAN KW kW kW AV76 ADF 76 0143 X10 Unsigned nvoS2FankW SNVT_power_kilo
Sys 2 Compressor Kw SYS 2 COMPRESSOR KW kW kW AV77 ADF 77 0144 X10 Unsigned nvoS2CompkW SNVT_power_kilo
AV78 ADF 78 0145 X1 Signed
AV79 ADF 79 0146 X1 Signed
AV80 ADF 80 0147 X1 Signed
AV81 ADF 81 0148 X1 Signed
AV82 ADF 82 0149 X1 Signed
AV83 ADF 83 0150 X1 Signed
AV84 ADF 84 0151 X1 Signed
AV85 ADF 85 0152 X1 Signed
AV86 ADF 86 0153 X1 Signed
BV54 BD 54 0185 N/A Signed
BV55 BD 55 0186 N/A Signed
BV56 BD 56 0187 N/A Signed
BV57 BD 57 0188 N/A Signed
BV58 BD 58 0189 N/A Signed
Sys 1 Operational Code AV SYS 1 OPERATIONAL CODE AV None None
See Status Codes Tab
Sys 1 Fault Code AV SYS 1 FAULT CODE AV None None
See Status Codes Tab
Sys 2 Operational Code AV SYS 2 OPERATIONAL CODE AV None None
See Status Codes Tab
Sys 2 Fault Code AV SYS 2 FAULT CODE AV None None
See Status Codes Tab
Free Cooling Mode AV [0=M,1=Fc,2=Hy]
FREE COOLING MODE AV If Free Cooling Enabled
0=Mechanical, 1=Free Cooling,
2=Hybrid
AV450 ADI 12 0131 X1 Unsigned nvoFreeCoolingMd SNVT_count