JOHNSON CONTROLS
5
Form 201.47-ICOM1
Issue date: 17/11/2022
ASHRAE 90.1 Compliant
Products are produced at a
facility w hose quality-
management systems are
ISO9001 certified.
LD23524b
Unit Nomenclature
Base Product Type
YVAA XX 46 A
Refrigerant
A = Refrigerant R-134a
B = Refrigerant R-513A
Voltage
17 = 200 / 3 / 60
28 = 230 / 3 / 60
40 = 380 / 3 / 60
42 = 400 / 3 / 60
46 = 460 / 3 / 60
50 = 380-415 / 3 / 50
51 = 415 / 3 / 50
58 = 575 / 3 / 60
0161 A
Y = YORK
V= Variable Speed Screw
A = Air Cooled Chiller
A = Design Series
Design Style
Modification Level
Unit Designator
B
Fan Quantity
The Control/VSD Cabinet contains lethal
high AC and DC voltages. Before per-
forming service inside the cabinet, remove
the AC supply feeding the chiller and
verify using a non-contact voltage sensor.
The DC voltage on the VSD DC Bus
will take 5 minutes to bleed o, after AC
power is removed. Always check the DC
Bus Voltage with a Voltmeter to ensure
the capacitor charge has bled o before
working on the system.
NEVER short out the DC Bus to dis-
charge the lter capacitors.
NEVER place loose tools, debris, or any
objects inside the Control Panel/VSD
Cabinet.
NEVER allow the Control Panel VSD
Cabinet doors to remain open if there is a
potential for rain to enter the panel. Keep
doors closed and ensure that all latches 
are engaged on each door unless the unit
is being serviced.
ALWAYS lockout the disconnect supply-
ing AC to the chiller.
The 1L Line Inductor will reach operating
temperatures of over 150°C (300°F.) DO
NOT open panel doors during operation.
Ensure that the inductor is cool whenever
working near the inductor with power
OFF.

Table of Contents