SECTION 4 - INSTALLATION
JOHNSON CONTROLS
53
Form 201.47-ICOM1
Issue date: 17/11/2022
4
STANDARD 2HP (with & Without VSD) CONDENSER FANS
FIELD WIRING LUGS TERMINAL BLOCK CIRCUIT BREAKER NON-FUSED DIS-
CONNECT SWITCH
YVAA-B MODEL EVAP INPUT
VOLTS
INPUT
FREQ
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
DUAL POINT WIRING
0491/1731 2605 200 60
230 60
380 60 3 #2 – 600
kcmil
3 3/0 -
400kcmil
3 3/0 -
400kcmil
400 60 3 #2 – 600
kcmil
3 3/0 -
400kcmil
3 3/0 -
400kcmil
400 50 3 #2 – 600
kcmil
3 3/0 -
400kcmil
3 3/0 -
400kcmil
460 60 2 #2 – 600
kcmil
2 #1 -
500kcmil
2 #1 -
500kcmil
575 60 2 #2 – 600
kcmil
2 #1 -
500kcmil
2 #1 -
500kcmil
0391/1381 2205/2605 200 60
230 60
380 60 3 #2 – 600
kcmil
3 3/0 -
400kcmil
3 3/0 -
400kcmil
400 60 3 #2 – 600
kcmil
3 3/0 -
400kcmil
3 3/0 -
400kcmil
400 50 3 #2 – 600
kcmil
3 3/0 -
400kcmil
3 3/0 -
400kcmil
460 60 2 #2 – 600
kcmil
2 #1 -
500kcmil
2 #1 -
500kcmil
575 60 2 #2 – 600
kcmil
2 #1 -
500kcmil
2 #1 -
500kcmil
0456/1606 2605 200 60
230 60
380 60 3 #2 – 600
kcmil
3 3/0 -
400kcmil
3 3/0 -
400kcmil
400 60 3 #2 – 600
kcmil
3 3/0 -
400kcmil
3 3/0 -
400kcmil
400
50 3 #2 – 600
kcmil
3 3/0 -
400kcmil
3 3/0 -
400kcmil
460
60 2 #2 – 600
kcmil
2 #1 -
500kcmil
2 #1 -
500kcmil
575 60 2 #2 – 600
kcmil
2 #1 -
500kcmil
2 #1 -
500kcmil
Table 4 - Electrical lug data (cont'd)