SECTION 5 - TECHNICAL DATA
JOHNSON CONTROLS
71
Form 201.47-ICOM1
Issue date: 17/11/2022
5
Note: The minimum and maximum ow rates listed here only represent the span of ows for a group of available evaporator options. Actual
chiller ow rates vary based on specic evaporator congurations. The application datasheet or nameplate must be referenced for specic ow
limits for every chiller.
Note: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Contact your Johnson Controls Sales Oce for ratings and further information.
All dimensions - in. (mm)
YVAA
Model
A B C1 C2 D
E-nozzle
size
Water
volume gal
(l)
Minimum
chilled water
ow rate
GPM (L/S)
Maximum
chilled
water ow
rate GPM
(L/S)
0219/0769
109.2
(2773)
121.2
(3078)
32.2
(818)
0.6
(15)
45.5
(1155)
5
31
(120)
150
(9.5)
910
(57)
0229/0809
152.9
(3883)
165.4
(4200)
24.0
(611)
0.6
(15)
45.9
(1165)
6
44
(170)
150
(9.5)
1300
(82)
0264/0924
152.9
(3883)
165.4
(4200)
24.0
(611)
0.6
(15)
45.9
(1165)
6
44
(170)
150
(9.5)
1300
(82)
0269/0949
152.0
(3860)
166.4
(4226)
28.8
(733)
0.6
(15)
47.0
(1193)
8
52
(200)
270
(17)
1570
(99)
0246/0866
152.9
(3883)
165.4
(4200)
24.0
(611)
0.6
(15)
45.9
(1165)
6
44
(170)
150
(9.5)
1300
(82)
0294/1034
152.0
(3860)
166.4
(4226)
28.8
(733)
0.6
(15)
47.0
(1193)
8
52
(200)
270
(17)
1570
(99)
0324/1134
152.0
(3860)
166.4
(4226)
28.8
(733)
0.6
(15)
47.0
(1193)
8
52
(200)
270
(17)
1570
(99)
0331/1161
152.0
(3860)
166.4
(4226)
28.8
(733)
0.6
(15)
47.0
(1193)
8
52
(200)
270
(17)
1570
(99)
0306/1076
152.0
(3860)
166.4
(4226)
28.8
(733)
0.6
(15)
47.0
(1193)
8
52
(200)
270
(17)
1570
(99)
0309/1089
152.0
(3860)
166.4
(4226)
28.8
(733)
0.6
(15)
47.0
(1193)
8
52
(200)
270
(17)
1570
(99)
0334/1174
152.0
(3860)
166.4
(4226)
28.8
(733)
0.6
(15)
47.0
(1193)
8
52
(200)
270
(17)
1570
(99)
Table 6 - Standard two-pass, right side inlet/outlet evaporator connections (cont'd)